Table 5-5 Other Parameters
Parameter name REF
Description
Ran
ge
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
StartDelay (s)
N/A
Startup delay time
(0,1200)
(5)
(5)
(5)
PVStartVolt(V)
7
PV start-up voltage
(860,950)
(900)
(900)
(900)
PVPowerMutate
Ratio (HECO)
35
Increasing Irradiation
Power Ramp Rate
{0.01%, 10%}
{5.00%}
{5.00%}
{5.00%}
GridFaultPStaStep N/A
Pwr Ramp after Fault {0.01%,100%}
{0.16%}
{2%}
{2%}
StopPowerStep
11
Manual Stop Pwr Rate {0.01%,100%}
{6.00%}
{2.00%}
{6.00%}
PsoftStaStep
N/A
Norm Start Pwr Rate {0.01%,100%}
{4.00%}
{2.00%}
{2.00%}
PDeratingStep
N/A Normal Pwr Derate Rate {0.01%,100%}
{6.00%}
{100.00%}
{6.00%}
StartUpTemp
N/A
Start Up Temperature
{-35, -20}
{-30}
{-30}
{-30}
FaultPowerT
N/A
IGBT Fault Temp
94.0C
94.0C
94.0C
94.0C
FaultEnvT
N/A
Enclosure Fault Temp
78.5C
78.5C
78.5C
78.5C
HVRTTripVol
10
HVRT Trigger Voltage {100%,135%}
{110%}
{110%}
{110%}
LVRTTripVol
9
LVRT Trigger Voltage
{70%,100%}
{80%}
{88%}
{88%}
LVRTPosCurrK
9 LVRT POS. current Coeff. {0%,300%}
{150%}
{150%}
{150%}
LVRTNegCurrK
9 LVRT NEG. current Coeff. {0%,300%}
{200%}
{20%}
{200%}
PSet_Pecent
3
Active power derate
{0%,110%}
{100%}
{100%}
{100%}
QSet_Pecent
2
Reactive power derate {-66%,66%}
{0%}
{0%}
{0%}
Risomin
36 Minimum insulation resist. {1k,2000k}
{100k}
{100k}
{100k}
GFCIStaProValue
27 Static Threshold Leakage
current
{50%,400%}
{100%}
{100%}
{100%}
GFCIStaProTime
27 Static Threshold Leakage
Time
{0,655}
{0.2}
{0.2}
{0.2}
GFCIDynProCoef
28
Threshold dynamic
coefficient Leakage
current
{0.0%,200%}
{100%}
{100%}
{100%}
DCIMax
30
Maximum DCI value
{0.1%,5.00%}
{0.50%}
{0.50%}
{0.50%}
DCIMax1Time
30 Trip time 1 of DCI value {0.00,120.00}
{60.00}
{60.00}
{60.00}
DCIMax2 (mA)
31
Maximum DCI value2
{5,5000}
{950}
{950}
{950}
DCIMax2Time
31 Trip time 2 of DCI value {0.00,120.00}
{1.00}
{1.00}
{1.00}
KprForRepeat
N/A Current Replication THDi {0%,100%}
{0%}
{0%}
{0%}
MPPTTime
4
MPPT Scan Cycle
{300,5400}
{3600}
{3600}
{3600}
CheckSumGroup
N/A
VirtualDamping
N/A
Virtual resistance
0.00 –
5.00Ω
0.000Ω
0.000Ω
0.000Ω
PHLoseRcvCoeff
42
Phase loss recover
coefficient
0.5% - 30.0%
2.0%
2.0%
2.0%
PhaseLoseVunbal
42
Phase loss fault Volt
Balance
0.01% - 10%
10%
10%
10%
PVSlowStartStep
42
PV slow start step
0.01% - 100%
10%
10%
10%
PhaseLoseCoeff
42
Phase loss fault
coefficient
0.5% - 30.0%
3.0%
3.0%
3.0%
Summary of Contents for SCH Series
Page 2: ......
Page 4: ......
Page 43: ...39 Figure 3 25 AC Output Cable Connection Distributed Wire box L1 L2 L3 ...
Page 45: ...41 Figure 3 27 AC Output Cable Connection Centralized Wire box Ver 2 ...
Page 58: ...54 Figure 4 1 System setting ...
Page 81: ...77 5 4 2 6 Others The REF column is reference to Table 5 7 Enable functions ...
Page 90: ...86 WiFi to Inverter ...
Page 92: ...88 ...
Page 93: ...89 5 5 History There are 2 submenus in the History menu Alarm and Running Status ...