80
Table 5-6 The Enable/Disable Parameters (IEEE1547, Rule21 and ISO-NE)
REF Parameter name
Description
Ran
ge
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
1 CtrlParaGroup
Control Loop
Parameters
{0,1,2,3,4}
{4}
{4}
{4}
2
CtrMode
ReactivePwMode
Reactive power
mode
Disable Dispatch
Remote Dispatch
Local Q
Locat PF
PF(P)
Q(U)
{Disable}
{Disable}
{Disable}
3 CtrMode
ActivePwMode
Active power mode
Disable Dispatch
Remote Dispatch
Local Control
{Disable}
{Disable}
{Disable}
4 MPPTScan
{Disable, Enable}
{Enable}
{Enable}
{Enable}
5 ArcEnable
AFCI
Not Available
{Disable, Enable}
{Disable}
{Disable}
{Disable}
6 ARCParaGroup
AFCI
Not Available
Reserved
Reserved
Reserved Reserved
7 VpvStartUpSetEn
PV Voltage Min.
{Disable, Enable}
{Disable}
{Disable}
{Disable}
8 Island Protect
Anti-Island
{Disable, Enable}
{Enable}
{Enable}
{Enable}
9
LVRTModeSetting
Disable
Enable No Q
Enable w/ Q
{Disable}
{Enable w/Q}
{Disable}
10
HVRTModeSetting
Disable
Enable No Q
Enable w/ Q
{Disable}
{Enable No
Q}
{Disable}
11 NormSoftStopPEn
SoftStopEn
soft
STOP
ramp
function
{Disable, Enable}
{Enable}
{Enable}
{Enable}
12
PID Check Settings
No External PID
External PID Box
Reserved
No External
PID Box
No External
PID Box
No External
PID Box
13 GridVolMax1En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
14 GridVolMax2En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
15 GridVolMax3En
Grid Protection
{Disable, Enable}
{Disable}
{Disable}
{Disable}
16 GridVolMin1En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
17 GridVolMin2En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
18 GridVolMin3En
Grid Protection
{Disable, Enable}
{Disable}
{Disable}
{Disable}
19 GridFrqMax1En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
20 GridFrqMax2En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
21 GridFrqMax3En
Grid Protection
{Disable, Enable}
{Disable}
{Disable}
{Disable}
22 GridFrqMin1En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
23 GridFrqMin2En
Grid Protection
{Disable, Enable}
{Enable}
{Enable}
{Enable}
24 GridFrqMin3En
Grid Protection
{Disable, Enable}
{Disable}
{Disable}
{Disable}
Summary of Contents for SCH Series
Page 2: ......
Page 4: ......
Page 43: ...39 Figure 3 25 AC Output Cable Connection Distributed Wire box L1 L2 L3 ...
Page 45: ...41 Figure 3 27 AC Output Cable Connection Centralized Wire box Ver 2 ...
Page 58: ...54 Figure 4 1 System setting ...
Page 81: ...77 5 4 2 6 Others The REF column is reference to Table 5 7 Enable functions ...
Page 90: ...86 WiFi to Inverter ...
Page 92: ...88 ...
Page 93: ...89 5 5 History There are 2 submenus in the History menu Alarm and Running Status ...