115
Table 6-19 Other Parameters
Only for CPS SCA50/60KTL-DO/US-480
Other Parameters
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min Defaul
t
Max
PowerOnDelay
(s)
Startup delay time
0
5
1200
0
5
1200
0
5
1200
ReactivePower
Step
(
%
)
Reactive Step
0.0
25.0
100.0
0.0
25.0
100.0
0.0
25.0
100.0
ErrSoftStartP
(%/P)
Power startup step
after Grid Fault
0.01
0.16
10
0.01
2
10
0.01
0.16
10
NormSoftStopP
(%/P)
Normal power step
in soft stop
0.01
6
100
0.01
10
100
0.01
10
100
NormSoftStartP
(%/P)
Normal power step
in soft startup
0.01
4
100
0.01
100
100
0.01
2
100
NormalDerating
Step
Power step in
Derarting
0.01
6
100
0.01
100
100
0.01
6
100
PVSlowStartSt
ep
(
%
)
PVSlowStartStep
0.01
10.00
100.00
0.01
10.00
100.00 0.01
10.00
100.00
PVSlowStartPw
Delta
(
%
)
The output power
should be slow
increased due to
the change of PV
illumination at the
Rule21 standard.
5.00
5.00
10.00
5.00
5.00
10.00
5.00
5.00
10.00
FaultPowerT
The trigger
temperature of
module (C)
95
95
95
95
95
95
95
95
95
FaultEnvT
The trigger
temperature of
enviroment (C)
83
83
83
83
83
83
83
83
83
GFCIStaticValu
e (mA)
The static
threshold value of
Leakage current
100
650
1000
100
650
1000
100
250
1000
Summary of Contents for SCA Series
Page 2: ......
Page 35: ...27 ...
Page 91: ...83 ...
Page 146: ...138 1 5 Figure 8 1 Replacing Cooling Fans 2 3 ...