116
Other Parameters
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min Defaul
t
Max
GFCIStaticT (s)
The static
threshold time of
Leakage current
0
0.20
655
0
0.20
655
0
0.20
655
GFCIDynProFa
ctor
The dynamic
trigger coefficient
of Leakage current
0
100
200
0
100
200
0
100
200
DCIProtection1
Maximum DCI
value1
0.01
2.50
5
0.01
2.50
5
0.01
0.50
5
DCIProtectio
nT1 (s)
Trip time 1 of
DCI
0
10
120
0
10
120
0
60
120
DCIProtectio
n2 (mA)
Maximum DCI
value2
5
950
5000
5
950
5000
5
950
5000
DCIProtection
T2 (s)
Trip time 2 of
DCI
0
1
120
0
1
120
0
1
120
PVStartVolt(
V)
PV start-up
voltage
300
330
400
300
330
400
300
330
400
MPPTScan
Period (s)
MPPT Scan
Cycle
300
3600
5400 300
3699
5400 300
3600
5400
ISOProtectio
n
(Ω)
Minimum
insulation
resistance
1k
100k
2000k 1k
100k
2000k 1k
100K
2000k
StarUPMinT
emp (C)
The minimum
startup
temperature
-35
-30
-20
-35
-30
-20
-35
-30
-20
Duplication
Group
Parameter of
repetitive
control
0
30
100
0
30
100
0
0
100
CtrParaGrou
p
The enabled
control
parameters
group.
0
4
4
0
4
4
0
4
4
Island
Protect
Island
enable/disabl
0
1
1
0
1
1
0
1
1