124
Inverter information
P1/2
Inverter Model:
Inverter SN: 0 0100 0000 0002
DSP Ver: 01.01.020×70DF DSP Boot:02.00
Data Logger Information
P2/2
IP 0.0.0.0
Data Logger SN 0 0000 0000 0000
Subnet Mask 0.0.0.0
DNS Server 0.0.0.0
Gateway 0.0.0.0
Address Range
Main Menu
Measurement Data
History Record
Power On/Off
Device Information
Setting
PmaxLim: SmaxLim:
HMI: 01.06 0×0100 HMI Boot:01.00
MiniMCU: 99.99 CPLD:15.00
Reserve
Figure 6-20 Device Information
This menu provides the information to identify the version of boards in the
inverter, model number, serial number and data logger information. This
information may be required when contacting CPS service.
6.6
Start-Up
Automatic start-up
: The inverter will start up automatically when the output
voltage and power of PV arrays meet the set value, AC power grid is normal,
and the ambient temperature is within allowable operating range.
Manual Power ON/OFF
: Manual Power ON/OFF is required after regulation
setting or manual (fault) shut-down. Press
ESC
to and
ENT
to access the
Main Menu, move the cursor to
“ON/OFF” and press
ENT
. Once in the
WARNING:
Please follow the guidelines below before on-grid operation to
eliminate possible dangers and to ensure safety.