![CPS SCA Series Installation And Operation Manual Download Page 129](http://html.mh-extra.com/html/cps/sca-series/sca-series_installation-and-operation-manual_2675129129.webp)
121
Other Parameters
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
Min
Default
Max
Min
Default
Max
olLowLim(V)
pt1
Mppt1_OptV
olUpLim(V)
OptiVoltMaxMp
pt1
200.0
1000.0
1500.0 200.0
1000.0
1500.0
Mppt2_OptV
olLowLim(V)
OptiVoltMinMp
pt2
200.0
200.0
1500.0 200.0
200.0
1500.0
Mppt2_OptV
olUpLim(V)
OptiVoltMaxMp
pt2
200.0
1000.0
1500.0 200.0
1000.0
1500.0
Mppt3_OptV
olLowLim(V)
OptiVoltMinMp
pt3
200.0
200.0
1500.0 200.0
200.0
1500.0
Mppt3_OptV
olUpLim(V)
OptiVoltMaxMp
pt3
200.0
1000.0
1500.0 200.0
1000.0
1500.0
Note:
Compatibility among the functions
1.
LVRT available another function will be fail as below:
Anti-islanding, QU, PF(P), PF Setting, reactive power setting, active
power setting, over frequency derating, GFCI, Grid over frequency
protection, Grid unbalance protection, DCI protection.
2.
Only one of these four functions can be valid at one time: QU, PF(P),
PF Setting and reactive power setting.
Summary of Contents for SCA Series
Page 2: ......
Page 35: ...27 ...
Page 91: ...83 ...
Page 146: ...138 1 5 Figure 8 1 Replacing Cooling Fans 2 3 ...