Recommendations Before Installation
See Chapter 10, Technical Data for specification ranges and limits.
NOTICE: DESIGN AND INSTALLATION RECOMMENDATIONS
Maintaining NEMA4X Rating in essential to assure safe operation of
the inverter. Water ingress is likely to cause a failure that could result
in an unsafe condition. The following are recommended
Addition of weep holes or any other hole will void the warranty.
For earlier wire box models with gland plate
– the conduit
connections must be strain reliefed to ensure the plate to gasket
interface is water tight. Water-tight metal flex conduit is one
method.
All conduit entries must be metallic to prevent propagation.
All conduit entries must be sealed to prevent moisture ingress.
o
Sealing conduits at the other end will provide additional
protection
– firestop putty may be used.
Separate conduits for + and
– DC cables may prevent arc
propagation outside of wire box.
NOTICE:
The allowable ambient temperature ranges for the
SCA25KTL-DO/US-208
、
SCA50KTL-DO/US-480 and SCA 60KTL
-DO/US-480 3-Phase String Inverters are defined based on the
following conditions:
Condition 1:
-40°C to 70°C, Inverter not installed, and in storage (in
packaging or unpackaged).
Condition 2:
-30°C to 60°C, Inverter installed, connected to electric
utility grid and operating during daylight hours.
Condition 3:
No low temp limit to 70°C, Inverter installed, connected
to electric utility grid but non-operating (daylight or nighttime hours).
Bulk head connector cover does not provide a water-tight seal.