2108h – Automatic blowing
Object 2108h is used to activate/deactivate the time-delayed automatic blowing function on each of
the modules on a LEMCOM island.
If the option is activated, the LEMCOM module automatically triggers blowing as soon as the
vacuum command is deactivated (the blowing duration is defined in object
The SDO command related to the Automatic Blowing option is the following:
Client (master)
server (LEMCOM)
CAN-ID
(600h+ID)
620h
Command
2Bh
Object L
08h
Object H
21h
Subindex
00h
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The Automatic Blowing option of each module (1 = active / 0 = inactive) is defined by the 16 bits of
bytes
Byte 1
– Byte 0
:
Byte 0
Byte 1
Automatic blowing option x x x x x x x x
x
x
x
x
x
x
x x
Module address
7 6 5 4 3 2 1 0 15 14 13 12 11 10 9 8
12.32
2109h – Duration of automatic blowing
Object 2109h is used to define the duration of automatic blowing on 2 bytes.
The SDO command used to define the blowing time is the following:
Client (master)
server (LEMCOM)
CAN-ID
(600h+ID)
620h
Command
2Bh
Object L
09h
Object H
21h
Subindex
Module no.+1
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The
subindex
is used to define the module to be set (from 1 to 16):
- Subindex = 0x01
set AUTO_BLOW_DURATION on master module (address #0)
- Subindex = 0x02
set AUTO_BLOW_DURATION on secondary module at address #1
-
…
- Subindex = 0x10
set AUTO_BLOW_DURATION on secondary module at address #15
Byte 1 - Byte 0
are used to define the value of AUTO_BLOW_DURATION.
AUTOMATIC BLOWING DURATION
The automatic blowing duration must range from 100 to 9999 ms (64h to 270Fh).
Default value: AUTO_BLOW_DURATION = 500 ms.