82
COSMOGAS
Ecotower
11 - TECHNICAL DATA
ECOTOWER
UM
Inverter air to water heat pump
Model
GB 06/STM 06
GB 09/STM 09
GB 13/STM 13
Main electrical supply
V/Hz/Ph
220-240 / 50 / 1
220-240 / 50 / 1
220-240 / 50 / 1
Refrigerant
kg
R410A / 1,3
R410A / 2,38
R410A / 2,95
Min./Max heat output
(1)
kW
1,98 / 6,21
4,33 / 10,10
4,2 / 12,6
Min./Max. electric absorption
(1)
W
490 / 1370
975 / 2153
926 / 3072
C.O.P 100% Capacity ratio/Max.
(1)
W/W
3,96 / 4,33
4,03 / 4,21
3,90 / 5,14
Min./Max. heating heat output
(2)
kW
1,80 / 5,15
4,19 / 9,53
3,76 / 11,5
Min./Max. electric absorption in heating
(2)
W
610 / 1710
1230 / 2990
1267 / 3723
C.O.P 100% Capacity ratio/Max.
(2)
W/W
2,95 / 3,35
3,12 / 3,30
2,97 / 3,42
Min./Max. cooling heat output
(3)
kW
2,95 / 5,8
4,10 / 6,84
4,29 / 10,37
Min./Max. electric absorption in cooling
(3)
W
750 / 2450
1230 / 3280
957 / 3156
E.E.R 100% Capacity ratio/Max.
(3)
W/W
3,81 / 3,95
3,62 / 3,65
3,84 / 4,63
Min./Max. cooling heat output
(4)
kW
2,6 / 4,88
2,34 / 5,05
2,34 / 7,91
Min./Max. electric absorption in cooling
(4)
W
840 / 1960
1080 / 3200
1000 / 3012
E.E.R 100% Capacity ratio/Max.
(4)
W/W
2,68 / 3,09
2,33 / 2,40
2,72 / 3,12
Circuit maximum pressure
bar
42
42
42
Compressor
Type
Twin Rotary
Twin Rotary
Twin Rotary
Quantity/System
1
1
1
Oil
FV50S
FV50S
FV50S
V.max Heating
Hz
85
74
85
V.max Cooling
Hz
85
66
79
Fan
Quantity
1
1
2
Air flow
m³/h
3000
3000
4200
Nominal power
W
60
60
120
Noise level
Internal/ external
dB (A)
35/56
35/56
35/59
Refrigerant connection
Liquid / Gas
“
1/4” / 1/2”
3/8” / 1/2”
3/8” / 5/8”
Net size (L×D×H)
Outdoor unit
mm
934×354×753
934×354×753
1123×400×1195
Indoor unit
mm
600x650x1720
600x650x1720
600x650x1720
Packaging dimensions (L×D×H)
Outdoor unit
mm
990×440×810
990×440×810
1330×490×1330
Indoor unit
mm
640x965x1914
640x965x1914
640x965x1914
Net weight
Outdoor unit
kg
61,5
62,5
113,0
Indoor unit
kg
140
140
140
Weight with packaging
Outdoor unit
kg
71,5
72,5
123,0
Indoor unit
kg
150
150
150
Outdoor operating temperature
Heating
°C
da -25 a 46
Cooling
°C
da 0 a 55
Limits of supply temperature
°C
da 7 a 75
Water volume
Kg
250
Maximum heating water pressure
MPa
0,3
Built-in electric heating heater
kW
1,5
Seasonal space heating energy efficiency (ηs)
kW
3+3
Efficienza energetica stagionale riscaldamento
d’ambiente (ηs)
%
175,6
156,6
152,9
(1) Heating condition: Return/supply water temperature : 30 °C/35 °C, outdoor temperature: BS/BU 7/6°C
(2) Heating condition: Return/supply water temperature : 40 °C/45 °C, outdoor temperature: BS/BU 7/6°C
(3) Cooling condition: Return/supply water temperature : 23 °C/18 °C, outdoor temperature: 35°C
(4) Cooling condition: Return/supply water temperature : 12 °C/7 °C, outdoor temperature: 35°C
Specifications are subject to change without notice. For current specifications refer to the adhesive labels on the equipment.