8 - USE
8.2.2.1 - Heating/Cooling outdoor reset
To proceed with a correct automatic setting of the calculated
supply temperature, it is advisable to set the values graphed on
the diagram of Figure 8-6 for heating or Figure 8-7 for cooling.
If these values do not give a satisfactory result, proceed with
the appropriate modifications taking into account that:
- Each parameter must be adjusted in small degrees;
- After each variation wait at least 24 hours to see the result;
- The more the adjustment parameter approaches the real
needs of the building, the more comfortable the heating
/ cooling of the building will be with high energy savings.
15
-20
35
20
350012_a
40
45
50
55
24
25
30
-15
-10
-5
0
5
10
15
20
25
30
35
10
5
0
Figure 8-6 - Heating Outdoor reset
Outdoor temperature (°C)
Supply temperature(°C)
Outdoor temp. 1
Outdoor temp. 2
W
ater temp. B
W
ater
temp. A