8.2.5 - NIGHT
The menu consists of several pages and, by scrolling with the
arrows, it is possible to consult and modify all the parameters
relating to heating setpoint:
Parameter
Permission level
U.M.
Range
Factory setting
Costum
value
Reduced setpoint
(Enabling or disabling of a reduced heating setpoint
according to the time bands to be set in the parameter
“Reduced setpoint timer”)
End user
/
Selected -
Not selected
Not selected
Temp. drop / rise
(reduction value of the heating setpoint respect to the
current setpoint as set manually or from the outdoor
reset)
End user
°C
2...10
5
Reduced setpoint timer
(time band during which the heating setpoint is
reduced by the value set in the parameter “Temp. drop
/ rise”)
End user
/
Quiet operation
(Enabling or disabling of the quiet operation. In this
mode, fans and compressor run at a reduced speed to
limit noise, at the expense of the overall efficiency of
the system)
End user
/
Selected -
Not selected
Not selected
Max allowable temp. drifting
(Maximum acceptable supply temperature reduction in
“quiet” mode)
End user
°C
2...10
8
Quiet operation timer
(“Quiet operation” activation time bands)
End user
/
8 - USE
Figure 8-11 - Night icon
8.2.6 - LEGIONELLA
This appliance is equipped with an buffer tank therefore it
is not necessary to carry out the anti-legionella cycle. It is
recommended not to change the following parameters:
Parameter
Permission level
U.M.
Range
Factory setting
Costum
value
Anti-legionella program (Don’t change)
End user
/
Selected -
Not selected
Not selected
Day and time (Don’t change)
End user
/
Setpoint (Don’t change)
End user
°C
60...75
70
Duration (Don’t change)
End user
Min
5...60
20
Finish time (Don’t change)
End user
Min
10...180
120
Figure 8-12 - Legionella icon