61
Ecotower
COSMOGAS
8.2.9 - WORKING MODE
The menu consists of several pages and, by scrolling with the
arrows, it is possible to consult and modify all the parameters
relating to the settings:
Parameter
Permission
level
U.M.
Range
Factory setting
Costum
value
Sanitary hot water
(Enabling or disabling of the DHW function)
Installer
/
Selected -
Not selected
Selected
Heating
(Enabling or disabling of the heating function)
Installer
/
Selected -
Not selected
Selected
Cooling
(Enabling or disabling of the cooling function)
Installer
/
Selected -
Not selected
Not selected
Basic operation mode
(Don’t change)
Installer
/
Selected -
Not selected
Not selected
Max duration for min compressor speed
Installer
Min
5...60
5
Heating / cooling switch
Installer
/
- OFF,
- Outdoor temp. (parame-
ter intervention threshold
“Outdoor temp. to start he-
ating” and “Outdoor temp.
to start cooling”),
- External signal control
(items “12” and “13” of Figu-
re 6-22),
- External signal control +
outdoor temp. (combina-
tion of the previous two
options).
OFF
Outdoor temp. to start heating
(Upon reaching this value, the machine waits an hour before re-
starting).
End user
°C
-10...25
18
Outdoor temp. to start cooling
(Upon reaching this value, the machine waits an hour before re-
starting).
End user
°C
20...-53
25
8 - USE
Figure 8-16 - Working mode icon