CT1001/CT1002 Touchscreen Programmable Thermostat
Installer Setup
Name
Settings
Notes
Initial
Setting
Record
Fan Control in
Heating
0-gas or oil furnace equipment controls fan in
heating (factory setting).
1-electric furnace thermostat controls fan in heating.
Only shown if conventional
system is selected. If heat
pump is chosen, fan defaults
to electric.
Changeover Valve
O/B Terminal
Energized in Heating
or Cooling (Heat
Pumps Only)
0-changeover valve O/B terminal setting.
1-changeover valve O/B terminal is energized in
heating.
Only shown if heat pump
system is chosen.
Backup Heat Source
(Auxiliary Heat)
0-heat pump backup heat source is electric (factory
setting).
1-heat pump backup heat source is fossil fuel.
Only shown if 2 heat/1 cool
or 3 heat/2 cool heat pump
is chosen.
External Fuel Fossil
Fuel Kit
0-no external fossil fuel kit is controlling heat pump
backup heat. This thermostat controls the dual fuel.
Must install outdoor sensor and set Installer Setup
Number 0340 to number 2. 1-external fossil fuel kit is
controlling heat pump backup heat.
Only shown if fossil fuel is
chosen as backup heat
source.
Cycles per hour (cph)
for 1st Stage
Compressor
3-cph recommended for compressors (factory
setting).
1, 2, 4, 5, 6-other cycle rate settings.
Cycles per hour (cph)
for 2nd Stage
Compressor
3-cph recommended for compressors (factory
setting).
1, 2, 4, 5, 6other cycle rate settings.
Only shown if two stages of
cool are selected.
Table 3. Installer Setup Menu. (CONTINUED)
51