Copley Controls Encoder Guide
Encoder Management
Copley Controls
49
ASCII Command using an External Application
A
drive’s RS-232 serial bus can be used by an external control application (HMI, PLC, PC, etc.) for
setup and direct serial control of the drive. The control application can issue drive commands from
the set of ASCII format commands that make up the Copley Controls ASCII Interface.
For example:
To clear
a driver’s encoder faults using an external control application, write a
1
to bit
7
of
the fault register
0xa4
.
See Copley’s ASCII Programmers Guide for more information.
CME 2 may also be used to send an ASCII command to clear latched
Encoder Faults
on the drive
as in the following procedure.
ASCII clear command via CME 2
1
From the Main screen, choose
Tools
ASCII Command Line
to open the tool.
2
Type
S R0xa4 0x80
in the
Command
field.
3
Press the
Enter
key to send the command to the amplifier. Observe the
Response
field.
The response should read
ok
.