USER'S MANUAL
•
The mounting rack of the outdoor unit shall be fastened with expansion bolt.
•
Ensure the secure installation regardless of what type of wall on which it is
installed, to prevent potential dropping that could hurt people.
•
Be sure to use the rated voltage and air conditioners dedicated circuit for the
power supply, and the power cable diameter must meet the national requirements.
•
When the maximum current of air conditioner is ≥16A, it must use the air switch
or leakage protection switch equipped with protection devices.
•
The operating range is 90%-1 0% of the local rated voltage.But insufficient
power supply malfunction, electrical shock, or fire. If the voltage instability,
proposed to increase the voltage regulator.
•
The minimum clearance between the air conditioner and the combustibles is 1.5 m.
•
The interconnection cord connect the indoor and outdoor units. You must first
choose the right cable size before preparing it for connection.
Cable Types: Outdoor Power Cable: H07RN-F or H05RN-F;
Interconnection cord: H07RN-F or H05RN-F;
•
Minimum Cross-Sectional Area of Power cable and interconnection cord.
•
The size of the interconnection cord, power cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. Refer to this
nameplate to choose the right cable, fuse, or switch.
Note :
Core number of cable refer to the detailed wiring diagram
adhered on the unit which you purchased.
Electrical Safety Requirements
Notices for installation
Rated Current of
Appliance(A)
AWG
Appliance
Amps(A)
Nominal Cross-
Sectional Area(mm² )
North America
Other Regions
10
>
3 and ≤ 6
>
6 and ≤ 10
>
10 and ≤ 16
>
16 and ≤ 25
>
25 and ≤ 32
>
32 and ≤ 40
13
18
25
30
18
16
14
12
10
40
8
0.75
1
1.5
2.5
4
6