62
USER'S MANUAL
•
When installing or repairing the air conditioner and the connecting line is not
long enough, the entire connecting line shall be replaced with the connecting
line of the original specification; extension is not allowed.
•
Use new connection pipe, unless re-flaring the pipe.
•
Avoid places of inflammable or explosive gas leakage or where there are
strongly aggressive gases.
•
Avoid places subject to strong artificial electric/magnetic fields.
•
Avoid places subject to noise and resonance.
•
Avoid severe natural conditions (e.g. heavy lampblack, strong sandy wind, direct
sunshine or high temperature heat sources).
•
Avoid places within the reach of children.
•
Shorten the connection between the indoor and outdoor units.
•
Select where it is easy to perform service and repair and where the ventilation
good.
•
The outdoor unit shall not be installed in any way that couldoccupy an aisle,
stairway, exit, fire escape, catwalk or any other public area.
•
The outdoor unit shall be installed as far as possible from thedoors and windows
of the neighbors as well as the green plants.
Requirements For Installation Position
•
Check nameplate of outdoor unit to make sure whether the refrigerant is R32.
•
Check the floor space of the room. The space shall not be less than usable
space(5m2) in the specification.The outdoor unit shall be installed at a
well-ventilated place.
•
Check the surrounding environment of installation site: R32 shall not be
installed in the enclosed reserved space of a building.
•
When using electric drill to make holes in the wall, check firstwhether there is
pre-buried pipeline for water, electricity and gas. It is suggested to use the
eserved hole in the roof of the wall.
Installation environment inspection
•
The mounting rack must meet the relevant national or industrial standards in
terms of strength with welding and connection areas rustproofed.
•
The mounting rack and its load carry surface shall be able to
withstand 4 times or above the weight of the unit, or 200kg, whichever is heavier.
Requirements of the mounting structure
Notices for installation