Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1510

APPLICATION

The ELPS502 model #M05 emergency lighting system is designed to automatically
provide illumination to designated areas during failure or interruption of power to the
normal lighting system. The ELPS502 is factory assembled and wired, and consists of one
ELPS50 power supply and two EVLA lighting fixtures.

When properly installed, the following raintight ELPS emergency lighting systems are UL
and cUL Listed for use in:

•  

ELPS50 Power Supply

- Class I, Division 1, Groups B, C & D

•  ELPS502 - Class I, Division 1, Groups B, C, D

Exit sign not UL/cUL       

•  ELPS502 (EXS/EXD) - Class I, Division 1 & 2, Groups C, D
(group B when ordered with GB suffix) 

All ELPS emergency lighting systems are suitable for use in Class II, Division 1, Groups E,
F, G and simultaneous presence hazardous (classified) areas as defined by the National
Electrical Code®.

The ELPS50 power supply consists of a battery supply and battery recharging system
housed inside a hazardous area enclosure with all the circuitry to automatically turn on
emergency DC lighting fixture(s) when the normal power supply fails. A pilot light indicates
when normal power is being supplied to the unit. A “push-to-test" push button switch is
provided for periodic testing of the unit.

Detail indication logic is given below

:

No Light     

AC power is removed from circuit

•  

Steady Light (No blinks)

Fully Charged

•   

Light Blinks Once

Charging

• - •  

Light Blinks Twice

Battery Failure

• - • - •  

Light Blinks Three Times

Circuit Failure

Immediately after supply power is initiated the indicating lamp will blink/pulse to indicate
that the unit is charging.  Once installed with supply power, the ELPS requires 72 hours to
charge the battery.  Once the unit has completed charging, the  indicating light will stop
blinking and go to steady.  Every six months, the unit will automatically perform a 90-
minute battery discharge test.  

At the completion of the test, if it is determined not to have met the 90 minute
requirement, the indicating lamp will display circuit failure (3 blinks).  At any time, if the
battery connection is not adequate the indicating lamp will display a battery failure (2
blinks).

The EVLA12 lighting fixture is a factory sealed assembly housing a single halogen
lamp/reflector light source.  ELPS EVI and ELPS EVA GB Exit Signs are factory sealed
with a single incandescent light source.  Lamps are included with all fixtures.

The EVLA12 is suitable for NEMA 4X locations when remote mounted (not installed on an
ELPS Power Supply) and supplied with a NEMA 4X breather/drain.

NOTE:

Ambient temperature at which ELPS50 power supply is rated  is 0ºC to 40ºC to

maximize battery capacity. EVLA12 lighting fixtures are permitted in higher, 55ºC ambient

temperature areas for more freedom in selecting remote installation location.

WARNING

To avoid personal injury, electric shock and equipment failure:

1. Do not use this equipment for other than intended use.

2. Do not use accessory equipment not recommended by the manufacturer.

3. Electrical power must be turned OFF before and during installation and

maintenance.

4. Equipment should be mounted in locations and at heights where it will not

readily be subjected to tampering by unauthorized personnel.

5. Do not mount near heat producing equipment.

6. In Class I areas, install and seal all equipment in accordance with the National

Electrical Code articles pertaining to Hazardous (Classified) Locations, plus any
other applicable codes.

7. Install only wiring systems with an equipment grounding conductor (which may

be the conduit system) to supply the ELPS.

8. two single-pole “Designated Disconnect” switches must be installed to

disconnect the  battery circuit and the supply circuit for safety in maintenance
and servicing.

9. Free installation area of hazardous atmospheres before wiring.

10. Observe all battery handling precautions contained herein.

11. Hammers or prying tools must not be allowed to damage the flat joint surfaces

of the ELPS50 power supply housing. Do not handle covers roughly, or place
them on surfaces that might damage or scratch the flat joint surfaces.

12. To avoid shattering: Do not operate lamp in excess of rated voltage, protect

lamp against abrasion and scratches, and against liquids when lamp is
operating. Dispose of lamp properly. 

EMERGENCY LIGHTING PRODUCTS

ELPS502(M05) SYSTEM, ELPS502(M05) EXS/EXD SYSTEM, 
ELPS50(M05) POWER SUPPLY, EVLA12 LIGHTING FIXTURE

National Electrical Code

®

is a registered Trademark of the National Fire Protection Association.

IMPORTANT

Emergency lighting system should be installed, inspected, operated, and maintained by

qualified and competent personnel.

RATINGS

ELPS50 Power Supply:

Input

-120, 220/240 and 277 VAC 

± 

5%,

50 or 60Hz

 -0.5 Amperes maximum

Output

-12 VDC; 2.5 Amperes
-28 Watts for 1½  hours (ELPS502)
-29 Watts for 1½  hours (ELPS502 EXS/EXD)

Ambient Temp:

-0ºC to 40ºC

Lamp Fixtures:

EVLA12

ELPS EVI/ELPS EVA GB

Input

-12 VDC

-12 VDC

Ambient Temp.

-55ºC maximum

-40ºC maximum

Operating Temp. Code

-Class I - T4A;

-Class I - T4

-Class II, III - T3C

-Class II, III - T3C

-Simultaneous Presence - T3C

Summary of Contents for ELPS50

Page 1: ...included with all fixtures The EVLA12 is suitable for NEMA 4X locations when remote mounted not installed on an ELPS Power Supply and supplied with a NEMA 4X breather drain NOTE Ambient temperature at...

Page 2: ...sen Nut A position lamp head in desired vertical position and retighten to 58 lb ft torque 4 Using the same 1 5 8 wrench loosen Nut B and position lamp head in desired horizontal position Be sure to r...

Page 3: ...VAC primary through designated disconnect to terminal 120 3 Connect 220 240 VAC primary through designated disconnect to terminal 220 240 4 Connect 277 VAC primary through designated disconnect to te...

Page 4: ...tates that Systems shall be tested periodically on a schedule acceptable to the authority having jurisdiction to assure their maintenance in proper operating condition It also states that A written re...

Page 5: ...stall lens ring by turning clockwise until threads are fully engaged All screw threads have been treated with a corrosion resistant lubricant Whenever disturbing threaded joints relubricate the thread...

Page 6: ...GRD 1 through L 7 6 Remove the mounting stud and pillar located in the uppermost left corner of the interior Remove the three other hold down nuts and lock washers on the aluminum backplate Remove the...

Page 7: ...ch and observe Main Power ON light should be OFF and the EVLA12 emergency light s should be ON 6 Lock the Designated disconnect switch ON to prevent unauthorized persons from turning system OFF 7 Cond...

Page 8: ...LATION AND MAINTENANCE INSTRUCTION SHEETS FOR METHODS OF TESTING All statements technical information and recommendations contained herein are based on information and tests we believe to be reliable...

Page 9: ...ts de normes NEMA 4X lorsque install distance n utilise pas un bloc d alimentation ELPS et fourni avec un reniflard purge REMARQUE pour maximiser la dur e de fonctionnement du bloc d alimentation ELPS...

Page 10: ...8 po desserrer l crou A positionner la t te du luminaire dans la position verticale voulue et resserrer l crou un couple de 58 lb pi 4 Utiliser la m me cl de 1 5 8 po desserrer l crou B et positionne...

Page 11: ...ivre le c blage de l alimentation EDS2129 EDS2129GB pour les applications de groupe B interrupteur sectionneur d sign pour installation distance non fourni Installer selon les directives fournies avec...

Page 12: ...s devraient tre test s r guli rement selon un programme acceptable par les autorit s qui ont juridiction pour assurer un bon tat de fonctionnement continuel Elle pr cise galement qu un registre par cr...

Page 13: ...de la lentille La tourner dans le sens horaire pour visser compl tement tout le filetage Tous les filets de la vis ont t enduits d un lubrifiant r sistant la corrosion D s qu un joint filet est manipu...

Page 14: ...n 3 Apr s avoir coup toutes les sources d alimentation du luminaire retirer toutes les attaches du couvercle pour acc der aux l ments internes 4 D brancher les fils de la lampe t moin et de l interrup...

Page 15: ...t moin Main Power ON alimentation principale pr sente devrait tre TEINTE et l clairage de s curit EVLA12 devrait FONCTIONNER 6 Verrouiller l interrupteur sectionneur d sign en position ON marche pour...

Page 16: ...DE DIRECTIVES D INSTALLATION ET D ENTRETIEN POUR CONNA TRE LES M THODES D ESSAI Toutes les d clarations tous les renseignements techniques et toutes les recommandations dans les pr sentes sont bas s...

Page 17: ...cesorios incluyen l mparas El EVLA12 est dise ado para reas NEMA 4X cuando se monta remotamente no se instala sobre una fuente de alimentaci n ELPS y se suministra con un respiradero drenaje NEMA 4X N...

Page 18: ...a llave de 1 5 8 afloje la Tuerca A coloque la cabeza de la l mpara en la posici n vertical deseada y apriete a 58 lb ft de torque 4 Con la misma llave de 1 5 8 afloje la Tuerca B y coloque la cabeza...

Page 19: ...GB para aplicaciones Grupo B Interruptor con montaje remoto no suministrado Instale seg n las instrucciones suministradas con el interruptor EDS2129 GB Realice el cableado a los terminales 8 y 9 Vea e...

Page 20: ...dicamente seg n un cronograma aceptable para las autoridades con jurisdicci n para garantizar su mantenimiento en condiciones de operaci n adecuadas Tambi n indica que se debe mantener un registro es...

Page 21: ...en Halogen G4 2 pins 14 watts 6 Instale el anillo de la lente girando en el sentido de las agujas del reloj hasta enroscarlo por completo Todas las cuerdas de los tornillos fueron tratadas con un lubr...

Page 22: ...tapa para acceder al interior 4 Desconecte las puntas de los cables en la l mpara piloto y el interruptor 5 Desconecte todas las conexiones entrantes de los terminales GRD 1 a L 7 6 Retire el perno de...

Page 23: ...r an estar encendidas 6 Configure el interruptor de desconexi n designado en ON para evitar que personas no autorizadas apaguen el sistema 7 Realice pruebas peri dicas de acuerdo con el Manual de Inst...

Page 24: ...EEMPLAZO DE L MPARA NOTAS HORA BATER A POR INDICAR UBICACI N DEL ACCESORIO DURACI N DE LA PRUEBA REGISTRO DE MANTENIMIENTO REQUISITOS NFPA 101 2003 SE DEBE REALIZAR UNA PRUEBA FUNCIONAL SOBRE TODOS LO...

Reviews: