background image

5

WARNING

10.   

Detection of flammable refrigerants

      • Under no circumstances shall potential sources of ignition be used in the searching for or detection of 
         refrigerant leaks.
      • A halide torch (or any other detector using a naked flame) shall not be used.

11. 

 Leak detection methods

      The following leak detection methods are deemed acceptable for systems containing flammable refrigerants:
      • Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be 
         adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) 
      • Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. 
      • Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to 
        the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. 
      • Leak  detection  fluids  are  suitable  for  use  with  most  refrigerants  but  the  use  of detergents containing 
        chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. 
      • If a leak is suspected, all naked flames shall be removed/ extinguished. 
      • If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the 
        system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 
      • Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing 
         process.

12.   

 Removal and evacuation

      • When breaking into the refrigerant circuit to make repairs – or for any other purpose   
        –conventional procedures shall be used. 
      • However, it is important that best practice is followed since flammability is a consideration.   
      • The following procedure shall be adhered to:
                  Remove refrigerant;  
                  Purge the circuit with inert gas;  
                  Evacuate; 
                  Purge again with inert gas; 
                  Open the circuit by cutting or brazing. 
      • The refrigerant charge shall be recovered into the correct recovery cylinders. 
      • The system shall be “flushed” with OFN to render the unit safe. 
      • This process may need to be repeated several times. 
      • Compressed air or oxygen shall not be used for this task.  
      • Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the 
         working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. 
      • This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used,
         the system shall be vented down to atmospheric pressure to enable work to take place. 
      • This operation is absolutely vital if brazing operations on the pipe-work are to take place. 
      • Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation 
         available.

13.   

Charging procedures

      • In addition to conventional charging procedures, the following requirements shall be followed: 
        - Ensure that contamination of different refrigerants does not occur when using charging equipment. 
        - Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. 
        - Cylinders shall be kept upright.  
        - Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. 
        - Label the system when charging is complete (if not already).  
        - Extreme care shall be taken not to overfill the refrigeration system. 
        - Prior to recharging the system it shall be pressure tested with OFN. 
      • The system shall be leak tested on completion of charging but prior to commissioning. 
      • A follow up leak test shall be carried out prior to leaving the site.

14.   

Decommissioning

      Before carrying out this procedure, it is essential that the technician is completely familiar 
      with the equipment and all its detail. 
      It is recommended good practice that all refrigerants are recovered safely. 
        

DC Inverter E

-

Series 

Duct Type

 Unit 

Summary of Contents for CH-ID0100RKE

Page 1: ...u have lost the Owner s Manual please contact the local agent or visit www cooperandhunter com or sent email to info cooperandhunter com or electronic version C H reserves the right to interpret this...

Page 2: ...Safety Notice 11 2 The Tools and Instruments for Installation 12 3 The Installation of the Indoor Unit 12 3 1 The Initial Check 12 3 2 Installation 13 4 Refrigerant Pipe 15 4 1 The Pipe Material 15 4...

Page 3: ...installed must have the reliable electrical grounding facility and protection Please do not connect the grounding of this product to various kinds of air feeding ducts drain piping lightning protecti...

Page 4: ...ating of circuit breakers ELB is detailed in outdoor instruction manual The method of connection of the appliance to the electrical supply and interconnection of separate components is detailed in bel...

Page 5: ...vapour being present while the work is being performed 6 3 General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Wor...

Page 6: ...ment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak dete...

Page 7: ...rcuit with inert gas Evacuate Purge again with inert gas Open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushe...

Page 8: ...cing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinder...

Page 9: ...uthority which authoriaes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification Servicing shall only be performed as recommended by the equi...

Page 10: ...ll be further specified in remote controller s manual Please read it carefully before using this appliance and keep it for future reference Remote controller optional ON OFF MODE FAN SLEEP SUPER SMART...

Page 11: ...essor must run for at least 5 minutes once operational In the 5 minutes compressor will not stop even the room temperature reaches the setting temperature point unless you use remote controller to tur...

Page 12: ...ng with mode interfere occurs Following shows the mode interfere scene Cooling Dry Heating Fan Cooling normal Dry mode interfere Heating Fan Outdoor unit always run with the mode of first indoor unit...

Page 13: ...irmly clamp the interconnecting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting all the wires be sure t...

Page 14: ...it mm unit mm During installation do not damage the insulation material on the surface of the indoor unit Number 1 2 3 4 5 6 7 Tool Standard screwdriver Vacuum pump Charge hose Pipe bender Adjustable...

Page 15: ...nd noise in electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if a one meter allowance is maintained Do not install the indoor un...

Page 16: ...from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed level by using a level or a plastic tube filled with water...

Page 17: ...rs 3 After finishing connecting the refrigerant pipes keep it warm with the insulation material Fig 4 4 Piping insulation procedure 030 071 085 100 125 160 DANGER The pipe go through the hole with the...

Page 18: ...e causing water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the included large sealing pad Drain piping connections Do...

Page 19: ...trol box 17 WARNING Fig 6 1 6 Electrical Wiring When clamping the wiring use the included clamping material as shown in the Fig 6 1 to prevent external pressure being exerted on the wiring connections...

Page 20: ...until display 17 and press ENTER button to entering system parameter adaption state symbol stop blinking Select desired parameter code 10 by pressing button and press ENTER button to confirm Select d...

Page 21: ...n the table are selected at the maximus current of the unit according to the European Standard En60 335 1 Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord c...

Page 22: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Reviews: