background image

16

5. Drain piping

·

Install the drain piping

·

 

Make sure the drain works properly .

 Prepare polyvinyl chloride pipe with a 32mm outer  

·

  diameter.

 The diameter of drain pipe connection hole should

·

  be same as that of the drain pipe.

 Keep the drain pipe short and sloping down wards at

·

  a gradient of at least 1/100 to prevent air pockets from 
  forming.

Water accumulating in the drain piping can cause 
the drain to clog.

Refrigerant 
pipes

Bucket

Portable pump

Air outlet

Drain outlet

CAUTION

CAUTION

·

To keep the drain tube from sagging, space hanging 

     wires every 1 to 1.5 m.

Use the drain hose and the clamp. Insert the drain 

·

    hose fully into the drain socket and firmly tighten the 
    drain hose and warm-keeping material with the clamp.  

The two areas below should be insulated because 

·

     condensation may happen there causing water leakage. 

·

Drain piping passing indoors
Drain sockets.

·

Referring the figure below, insulate the drain socket 

·

    and drain hose using the included large sealing pad.

Drain piping connections

·

Do not connect the drain pipes directly to sewage pipes

    to avoid ammonia odour. The ammonia in the sewage 
    might enter the indoor unit through the drain pipes and 
    corrode  the heat exchanger.

·

Do not twist or bend the drain hose, doing so applies

    excessive force applied on it and may also cause 
    leakage.

·

After piping work is finished, check if drainage flows

    smoothly.

·

Gradually pour approximately 1000 cc of water from

    the outlet hole into the drain pan to check drainage flow.

·

Check the drainage as shown below:

Drain hose

Sealing material

Sealing material

When

 

the

 

relative

 

humidity of inlet or ambient air

exceeds 80%,apply an (field-supplied) auxiliary 
drain pan beneath the indoor unit as shown below.

Indoor Unit

To the Atmosphere

(Field-Supplied)

Auxiliary Drain Pan

DC Inverter E

-

Series 

Duct Type

 Unit 

Summary of Contents for CH-ID0100RKE

Page 1: ...u have lost the Owner s Manual please contact the local agent or visit www cooperandhunter com or sent email to info cooperandhunter com or electronic version C H reserves the right to interpret this...

Page 2: ...Safety Notice 11 2 The Tools and Instruments for Installation 12 3 The Installation of the Indoor Unit 12 3 1 The Initial Check 12 3 2 Installation 13 4 Refrigerant Pipe 15 4 1 The Pipe Material 15 4...

Page 3: ...installed must have the reliable electrical grounding facility and protection Please do not connect the grounding of this product to various kinds of air feeding ducts drain piping lightning protecti...

Page 4: ...ating of circuit breakers ELB is detailed in outdoor instruction manual The method of connection of the appliance to the electrical supply and interconnection of separate components is detailed in bel...

Page 5: ...vapour being present while the work is being performed 6 3 General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Wor...

Page 6: ...ment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak dete...

Page 7: ...rcuit with inert gas Evacuate Purge again with inert gas Open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushe...

Page 8: ...cing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinder...

Page 9: ...uthority which authoriaes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification Servicing shall only be performed as recommended by the equi...

Page 10: ...ll be further specified in remote controller s manual Please read it carefully before using this appliance and keep it for future reference Remote controller optional ON OFF MODE FAN SLEEP SUPER SMART...

Page 11: ...essor must run for at least 5 minutes once operational In the 5 minutes compressor will not stop even the room temperature reaches the setting temperature point unless you use remote controller to tur...

Page 12: ...ng with mode interfere occurs Following shows the mode interfere scene Cooling Dry Heating Fan Cooling normal Dry mode interfere Heating Fan Outdoor unit always run with the mode of first indoor unit...

Page 13: ...irmly clamp the interconnecting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting all the wires be sure t...

Page 14: ...it mm unit mm During installation do not damage the insulation material on the surface of the indoor unit Number 1 2 3 4 5 6 7 Tool Standard screwdriver Vacuum pump Charge hose Pipe bender Adjustable...

Page 15: ...nd noise in electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if a one meter allowance is maintained Do not install the indoor un...

Page 16: ...from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed level by using a level or a plastic tube filled with water...

Page 17: ...rs 3 After finishing connecting the refrigerant pipes keep it warm with the insulation material Fig 4 4 Piping insulation procedure 030 071 085 100 125 160 DANGER The pipe go through the hole with the...

Page 18: ...e causing water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the included large sealing pad Drain piping connections Do...

Page 19: ...trol box 17 WARNING Fig 6 1 6 Electrical Wiring When clamping the wiring use the included clamping material as shown in the Fig 6 1 to prevent external pressure being exerted on the wiring connections...

Page 20: ...until display 17 and press ENTER button to entering system parameter adaption state symbol stop blinking Select desired parameter code 10 by pressing button and press ENTER button to confirm Select d...

Page 21: ...n the table are selected at the maximus current of the unit according to the European Standard En60 335 1 Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord c...

Page 22: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Reviews: