background image

3.2 Installation

3.2.1 Suspension bolts
(1) Consider the pipe direction, wiring and maintenance 
     carefully, and choose the proper direction and location 
     for installation.
(2) Install the suspension bolts as shown in Fig. 3.2 
      below.

Fig. 3.2.1 Fixing the suspension bolts 

·

For the concrete

·

For the steel beam

·

For the wooden beam

150 to160mm

Screw in

100 to150kg

Steel bar

Concrete

Suspension bolts

(W3/8 or M10)

  

                   

                  

 shaped steel beam

Wood rib 

60mm to 90mm 

Wooden beam

Nut 

Round washer

Square washer

Suspension bolts

13

3.2.2 The position of the suspension bolts and the pipes

(1) Mark the positions of the suspension bolts, the 
     positions of the refrigerant pipes and the drain pipes.
(2) The dimension are shown below.

·

Optimum air distribution is ensured.

·

The air passage is not blocked.

·

Condensate can drain properly.

·

The ceiling is strong enough to bear the weight of the 

    indoor unit.

·

A false ceiling does not seem to be at an incline.

·

Sufficient clearance for maintenance and servicing 

    is ensured.(See Fig.3.1.1,Fig3.1.2 )

·

Piping between the indoor and outdoor units is within 

    the allowable limits.(refer to the installation of the 
    outdoor unit )

·

The indoor unit, outdoor unit, power supply wiring 

    and transmission wiring must be kept at least 1 meter 
    away from televisions and radio, this prevents image 
    interference and noise in electrical appliances. 
   (Noise may be generated depending on the conditions 
    under which the electric wave is generated, even if a 
    one-meter allowance is maintained.)

·

Do not install the indoor unit in a machinery shop or 

    kitchen where vapor from oil or its mist flows to the 
    indoor unit. The oil will deposit on the heat exchanger, 
    thereby reducing the performance of the indoor unit, 
    and may deform and in the worst case, break the 

  

plastic parts of the indoor unit.
Use suspension bolts to install the unit, check whether 

·

    or not the ceiling is strong enough to support the 
    weight of the unit. If there is a risk that the ceiling is 
    not strong enough, reinforce the ceiling before 
    installing the unit. 
    For bottom intake(42K~60K), replace the chamber 
    lid and the intake-side flange in the procedure listed 
    in below figures.
 (1)  Remove the intake-side flange, then remove the 
      chamber lid. Refer to Fig. 3.1.3 for the directions.
 (2) Reattach the removed chamber lid in the orientation 
      shown in Fig. 3.1.4, reattach the removed intake-side 
      flange in the orientation as shown in Fig. 3.1.4.

Suspension bolts

(W3/8 or M10)

Nut 

Fig. 3.1.3

Fig. 3.1.4

Intake-side flange

Chamber lid

Intake-side flange

Chamber lid

Filter

(

invalid

 

for

Filter

(

invalid

 

for

 

some

 

models

)

some

 

models

)

.1

Fig. 3.3 Suspension bolts

(Unit:mm)

a

b

c

d

Air outlet

Air inlet

Model

(Cooling capacity)

a

b

c

d

0

30

/0

35

961

910

375

447

0

50

/0

71

1231

1180

375

447

0

85

/1

00

1177

1140

666

720

1

25

/1

40

/1

60

1334

1300

756

800

DC Inverter E

-

Series 

Duct Type

 Unit 

Summary of Contents for CH-ID0100RKE

Page 1: ...u have lost the Owner s Manual please contact the local agent or visit www cooperandhunter com or sent email to info cooperandhunter com or electronic version C H reserves the right to interpret this...

Page 2: ...Safety Notice 11 2 The Tools and Instruments for Installation 12 3 The Installation of the Indoor Unit 12 3 1 The Initial Check 12 3 2 Installation 13 4 Refrigerant Pipe 15 4 1 The Pipe Material 15 4...

Page 3: ...installed must have the reliable electrical grounding facility and protection Please do not connect the grounding of this product to various kinds of air feeding ducts drain piping lightning protecti...

Page 4: ...ating of circuit breakers ELB is detailed in outdoor instruction manual The method of connection of the appliance to the electrical supply and interconnection of separate components is detailed in bel...

Page 5: ...vapour being present while the work is being performed 6 3 General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Wor...

Page 6: ...ment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing then a permanently operating form of leak dete...

Page 7: ...rcuit with inert gas Evacuate Purge again with inert gas Open the circuit by cutting or brazing The refrigerant charge shall be recovered into the correct recovery cylinders The system shall be flushe...

Page 8: ...cing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinder...

Page 9: ...uthority which authoriaes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification Servicing shall only be performed as recommended by the equi...

Page 10: ...ll be further specified in remote controller s manual Please read it carefully before using this appliance and keep it for future reference Remote controller optional ON OFF MODE FAN SLEEP SUPER SMART...

Page 11: ...essor must run for at least 5 minutes once operational In the 5 minutes compressor will not stop even the room temperature reaches the setting temperature point unless you use remote controller to tur...

Page 12: ...ng with mode interfere occurs Following shows the mode interfere scene Cooling Dry Heating Fan Cooling normal Dry mode interfere Heating Fan Outdoor unit always run with the mode of first indoor unit...

Page 13: ...irmly clamp the interconnecting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting all the wires be sure t...

Page 14: ...it mm unit mm During installation do not damage the insulation material on the surface of the indoor unit Number 1 2 3 4 5 6 7 Tool Standard screwdriver Vacuum pump Charge hose Pipe bender Adjustable...

Page 15: ...nd noise in electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if a one meter allowance is maintained Do not install the indoor un...

Page 16: ...from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed level by using a level or a plastic tube filled with water...

Page 17: ...rs 3 After finishing connecting the refrigerant pipes keep it warm with the insulation material Fig 4 4 Piping insulation procedure 030 071 085 100 125 160 DANGER The pipe go through the hole with the...

Page 18: ...e causing water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the included large sealing pad Drain piping connections Do...

Page 19: ...trol box 17 WARNING Fig 6 1 6 Electrical Wiring When clamping the wiring use the included clamping material as shown in the Fig 6 1 to prevent external pressure being exerted on the wiring connections...

Page 20: ...until display 17 and press ENTER button to entering system parameter adaption state symbol stop blinking Select desired parameter code 10 by pressing button and press ENTER button to confirm Select d...

Page 21: ...n the table are selected at the maximus current of the unit according to the European Standard En60 335 1 Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord c...

Page 22: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Reviews: