18
Model
(Capacity
Btu/h)
The range
of
static pressure
Function
code
set
0
30
/0
35
/0
50
0-50Pa
0-50, more than 50 is 50 Pa,
[default: 0 (0Pa)]
0
71
0-40Pa
0-40, more than 40 is 40 Pa,
[default: 0 (0Pa)]
0
85
/1
00
0-120Pa
1-120, more than 120 is 120 Pa,
[default: 0 (47Pa)]
1
25
/1
40
/1
60
0-120Pa
1-120, more than 120
is 120 Pa
,
[
default:
0 (60Pa)
]
Static pressure setting:
Hold down both“MODE”button and“ADD.FUNC.”button for 3 seconds, symbol and parameter code
blinking at the same time.
Press“ / ”button to adjust parameter number until display “17”, and press “ENTER”button to entering
system parameter adaption state, symbol stop blinking.
Select desired parameter code 10 by pressing
“ / ”
button , and press "ENTER" button to confirm.
Select desired function code to rewrite the parameter values by pressing “ /
”
button , and press
"ENTER" button to confirm.
Press “ON/OFF”button or “CANCEL”button to quit.
Parameter Code
LCD
Function Code
Error Indicator
1
2
3
4
5
If you still have any trouble, please contact local technical service center of our company for further information.
Fig 6.2.2
The static pressure can be freely adjusted by using specific wire remote controller.
6.2 Change of Static Pressure
DC Inverter E
-
Series
Duct Type
Unit