“STATUS WORD” parameter STA60M
VALUE
CONFIGURATION
16
Temperature display in “big area” and all enabled with Set settable 10-35 °C
17
Temperature display in “big area” and FAN key “disabled” with Set settable 10-35 °C
18
Temperature display in “big area” and CLOCK key “disabled” with Set settable 10-35 °C
19
Display Set in “big area” and all enabled with Set adjustable from 10 to 35 °C
20
Display Set in “big area” and and FAN key “disabled” with Set adjustable from 10 to 35 °C
21
Display Set in “big area” and CLOCK key “disabled” with Set settable 10-35 °C
22
Temperature display in “big area” and all enabled with Set adju - X (X defined by configurator X maximum 5 °C).
23
Temperature display in “big area” and FAN key “disabled” with Set adju - X (X defined by configurator X
maximum 5 °C).
24
Temperature display in “big area” and CLOCK key “disabled” with Set adju - X (X defined by configurator X
maximum 5 °C).
“STATUS WORD” parameter STA70M
VALUE
CONFIGURAZIONE
32
Temperature display
33
Setpoint display
“STATUS WORD” parameter NR9001
BIT
Description
“0”
“1”
Default
0
Operation Mode
Remote (Disable digital input Comfort/
Economy and Power Off)
Local (Enable digital input Comfort/
Economy and Power Off)
0
1
Ambient Temperature
Remote (comes from STA60M or
STA70M)
Local (comes from “dedicated”
analogue input S1)
0
2
Summer / Winter Changeover
Remote (Disable digital input Summer/
Winter DI3)
Local (Enable digital input Summer/
Winter DI3)
1
3
Temperature Set
Remote (comes from NR9000-RT)
Local (comes from “dedicated”
analogue input S2)
0
4
Window Contact
Disable digital input DI1
Enable digital input DI1
0
5
Temperature Set Correction Mode
10-35 °C
±3K
0
6
DIP switch
Enable
Disable
0
7
Electrical Battery
Disable
Enable
0
Functions STA60M sensors
Through STA60M sensor the user is able to:
•
set regulation setpoint;
•
set the operating mode;
•
set fan speeds;
•
set time tables;
•
set Modbus communication parameters as baud rate and Modbus address.
Functions STA70M sensors
Through the STA70M sensor the user is able to:
•
set regulation setpoint;
•
set the operating mode;
•
set fan speeds;
•
set time tables;
•
set Modbus communication parameters as baud rate and Modbus address.
1
st
Issue
06/2019
DBL585e
Page 16