STA60M and STA70M sensors require an initial configuration to be 

performed during start-up. Below is the information to make the 

initial settings of both sensors.

STA60M SENSORS

STA60M sensor is a room terminal that allows the user to adjust the 

temperature in an environment. It communicates with the Modbus 

protocol and can be connected to the NR9001 controller.

Depending on the models, the power supply can be 24 Vac/dc or 

230 Vac.

Configuration

STA60M sensor, in order to be connected to the 485 bus of the NR9001 

controller, requires a preconfiguration with regard to the communi

-

cation speed and the Modbus address.

Procedure:

1.  Press the FAN and POWER buttons simultane-

ously for 3 sec. to enter the Parameter Menu.

2. 

Turn the knob to set the number 22 above the 

wording  and  press  the  knob  to  confirm.  The 

word “Addr” appears.

3. 

Press the knob to confirm the desire to set the 

Modbus address.

4. 

Turn  the  knob  to  set  the  address  (1  -  9)  and 

press the knob to confirm.

5. 

Turn the knob until the word “Baud” appears

6. 

Press the knob to confirm the desire to set the 

communication speed.

7. 

Turn the knob to set the value 1 (9600 baud) 

and press the knob to confirm.

8. 

Turn  the  knob  until  the  word  “esc”  appears 

and press the knob to exit the configuration.

Note: the sensor address must be univocal, sequen

-

tial and start from 1.

Clock setting

STA60M sensor has a clock inside which therefore needs to be set.

Procedure:

1. 

Press  the  Clock  button  for  3  sec.  The  word 

“Cloc” appears.

2. 

Press the knob to confirm you want to set the 

time. The cursor flashes on the hour.

3. 

Turn  the  knob  to  set  the  desired  value  and 

press the knob to confirm. The cursor flashes on 

the minutes.

4. 

Turn  the  knob  to  set  the  desired  value  and 

press the knob to confirm. The cursor flashes on 

the day of the week.

5. 

Turn the knob to set the desired day and press 

the knob to confirm. The word “Cloc” appears 

again.

6. 

Turn  the  knob  until  the  word  “esc”  appears 

and press the knob to exit the configuration.

Setting schedules

STA60M sensor has a schedule inside it with the possibility, for each 

day, to set a maximum of 6 time bands.

The compilation of the schedule consists of setting the desired Tem-

perature Set for each band.

In addition to the Set there is also the possibility of setting the OFF sta-

tus which for the controller has the meaning of antifreeze protection.

Procedure:

1. 

Press the Clock button for 3 sec. The word “Cloc” appears.

2. 

Turn the knob until the word “time band” appears.

3. 

Press the knob to confirm the intention to set the time programs. 

The word “Sel days” appears.

4. 

Turn the knob to select the groups of days or 

the single day for which you want to set the 

time table.

5. 

Press the knob to set the first time band: a sym

-

bol representing it flashes on the right.

FASCIA ORARIA 1

FASCIA ORARIA 2

FASCIA ORARIA 3

FASCIA ORARIA 4

FASCIA ORARIA 5

FASCIA ORARIA 6

6. 

Turn the knob to select the desired band and 

press the knob to confirm. The cursor flashes on 

the hour.

7. 

Turn the knob to set the desired time and press 

the knob to confirm. The cursor flashes on the 

minutes.

8. 

Turn the knob to set the minutes and press the 

knob to confirm. The cursor flashes in the field to set the set.

9. 

Turn the knob to set the desired temperature value and press 

the knob to confirm. The cursor flashes on the symbol represen

-

ting the time slot.

10.  Repeat the steps from point 6 to set the fol-

lowing time bands (max 6).

11. 

To end the settings, turn the knob clockwise un

-

til “esc” is displayed and press the knob to con

-

firm that you wish to exit. The word “sel days” 

appears.

12. 

Turn  the  knob  counterclockwise  until  “esc”  is 

displayed and press the knob to confirm that 

you wish to exit. The word “time band” appe-

ars.

13. 

Turn  the  knob  clockwise  until  “esc”  appears 

and press the knob to exit the time program

-

ming.

Switching off schedule

To switching off a schedule, repeat the setting pro-

cedure and in step 6 (setting the time) select the 

dash screen with the knob.

Navigation

STA60 sensor can have different configurations that are sent by the 

controller based on the configuration performed by the Configura

-

tor.

Stationing page

Depending on the configuration, the temperature 

or room temperature set and the Clock are shown.

Turning the knob allows you to set the Room tempe

-

rature set or make a Set correction (+ - K).

The room temperature shown on the display will be 

that of the STA60M sensor or, if present and configu

-

1

st

 Issue

06/2019

DBL585e

Page 17

Summary of Contents for Energon NR9001

Page 1: ...have a different meaning if changeover auto instead of Aux Loop function is disabled from the configuration tool S4 sensor is used to switch the controller operation mode to Energon Fan Coil Digital C...

Page 2: ...set at 9013 ModBus address 1 BUS output for Modbus supervisor connection 1 BUS output for STA60M or STA70M sensor connection For any customizations related to the controller configuration con tact th...

Page 3: ...I3 input digital 3 24Vac Summer Winter contact 37 DI4 input digital 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input...

Page 4: ...of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 4 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Change...

Page 5: ...pe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 5 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 6: ...e plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 6 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 7: ...pe plant with 24V 3 points valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 7 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 8: ...0 copper wire plait type twisted shielded braided and insulated The shield must be connected to controller GND pin 25 The network must be wired only in accordance with the principle shown here called...

Page 9: ...e the regula tion If the fan is connected to the relay output it is necessary to set the minimum fan speed parameter at 1 A system configuration with Proportional Fan requires setting the minimum spee...

Page 10: ...sed in parallel In case of use of 3 speed fans 3 relays the 0 10V outputs are always available and they follow the ON OFF or 3 point valves characteris tics The diagrams of the valves and fans share t...

Page 11: ...Propor tional Band as shown in the diagram aside 2 ON OFF Valves and 3 Speed FAN The valves are activated in ON OFF mode with a hysteresis Speed 1 2 and 3 follow to the Pro portional Band as shown in...

Page 12: ...alves 3 point or 0 10V and 3 speed fan The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 6 ON OFF V...

Page 13: ...llow the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated...

Page 14: ...luid is the RED LED NR9001 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top co ver and 2 LEDs to identify the state of the valves open or closed and th...

Page 15: ...Automatic changeover min set 10 35 20 Automatic changeover max set 10 35 30 Fan min limit set 10 55 35 Fan min limit hysteresis 0 10 3 Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay T...

Page 16: ...nt display STATUS WORD parameter NR9001 BIT Description 0 1 Default 0 Operation Mode Remote Disable digital input Comfort Economy and Power Off Local Enable digital input Comfort Economy and Power Off...

Page 17: ...of the schedule consists of setting the desired Tem perature Set for each band In addition to the Set there is also the possibility of setting the OFF sta tus which for the controller has the meaning...

Page 18: ...g the Knob it is possible to display cyclical ly the alarm error code the Modbus address of the controller and the main page ON OFF FAN buttons a long press of the two buttons allows entering the conf...

Page 19: ...e The parameters Dead band and Set Economy allow to determi ne the Set of Cold Set of Hot Dead band the set in Eco C Set C Rid Set the Eco Set F Set F Rid Set Instead for a more inuitive management th...

Page 20: ...ed in EEPROM memory The address can be changed only if the controller Dipswitch is not active If the STA70M sensor is present the Modbus address cannot be set by Supervision Contact our technical secr...

Page 21: ...performances stated in this sheet can be modified without any prior notice DIMENSIONS mm NR9001 STA60M STA60M 2 STA60MP STA60MP 2 86 86 8 22 55 28 48 74 60 74 60 1st Issue 06 2019 DBL585e Page 21 STA...

Reviews: