of  the  relays.  The  second  type  of  ventilation  manages  an  inverter 

through an analogue output 0 - 10 V.

For  ventilation  to  3  fixed  speeds,  set  the  “minimum  speed  limit”,  it 

means keeping the fan speed 1 even when the set is satisfied. While 

it has no action on the “Maximum Speed   Limit.”

The proportional ventilation, instead, uses the “Minimum speed limit” 

to protect the motor from burning (the motor is driven with low signals 

but does not rotate) and the “Maximum speed limit” to reduce noise 

at high speeds, due to turbulence in air ducts.

The switching on and off are managed by a hysteresis determined 

by the same value of the Minimum Limit.

The setting of the Flag “Fan min at set point” keeps the fan speed to 

the minimum limit set also when set is satisfied.

Involved parameters:

Ventilation minimum limit = 0

Ventilation maximum limit = 100

Fan at minimum speed @ satisfied set = NO

Heating loop set = 20°C

Fan proportional band = 3

Valve proportional band ON/OFF = 1 

Plant = 2 pipes

Loop = heating

Control modes

NR9001 works with 8 different control modes selectable via dip switch 

or by supervisory system:

1.

 ON/OFF Valves and 3-speed fan (“FAST” operation mode - Oper-

ation Diagram 1).

2.

 ON/OFF Valves and 3-speed fan (Operation Diagram 2).

3.

 Proportional Valves (3 point or 0-10V) and 3-speed fan (Operation 

Diagram 3).

4.

 ON/OFF Valves and 1-speed fan (Operation Diagram 4).

5.

 Proportional Valves (3 point or 0-10V) and 1-speed fan (Operation 

Diagram 5).

6.

 ON/OFF Valves and Modulating FAN (0–10V) (Operation Diagram 

6).

7a.

 2-pipe plant. Proportional Valve (0-10V) and Modulating Fan (0-

10V) (Operation Diagram 7a).

7b.

 4-pipe plant: Sequence Valves 0-5/6-10V and Modulating Fan 

(0-10V) (Operation Diagram 7b).

8.

 3-point Valves and Modulating Fan (0-10V) (Operation Diagram 

8).

When using ON / OFF valves and three points, the modulating valves 

that share the same temperature set point and the same proportion-

al band can also be used in parallel.

In case of use of 3-speed fans (3 relays), the 0-10V outputs are always 

available and they follow the ON-OFF or 3-point valves characteris

-

tics.

The diagrams of the valves and fans share the Set point, instead pro

-

portional bands and hysteresis can be set independently. 

It is possible to enable the functions hot/cold launch, “disposal” and 

minimum speed activation with a priority over normal operation de

-

fined by the diagrams.

Badge Function

This function can be activated in the tools setting “Function Bagde 

= ON”.

In this case the “Forcing regime from local inputs” is disabled and the 

digital input D12 is used. The presence of the badge (DI2 = closed) 

switches the controller in Comfort mode, while the absence switches 

into Economy mode. In addition, the presence of the badge ena-

bles the management of electrical loads through the OC1 output 

and the absence disables them with a delay of 30 sec.

Through  supervision,  if  present,  it  is  possible  to  force  the  operating 

mode independently if the badge function is active or not.

Through STA60M or STA70M sensor, if present, it is possible to force the 

operating mode only if the badge function is active.
Only if the badge function is active the electrical loads can be en

-

abled.

Min. Limit and Max Range Set

Through  the  configurator  you  can  define  the  minimum  and  maxi

-

mum value (in the 10-35 range) of the temperature set in STA60M or 

STA70M sensors. By setting the minimum and maximum value for the 

same value is obtained a fixed-point operation.

Max value of correction of the Set

Through the configurator it is possible to define the maximum value 

of corr - of the Set (range 0 - 5).

Through the STA60M or STA70M sensors you can set the values within 

the set values.

Manual ventilation shutdown at set satisfied

If the function is enabled, the fan is stopped at a satisfied set even if 

there has been a manual forcing.

The default function is enabled and through the configurator (Fan 

Manual OFF @ Set satisfied) it can be disabled, thus maintaining the 

fan speed forced by the user.

1

st

 Issue

06/2019

DBL585e

Page 10

Summary of Contents for Energon NR9001

Page 1: ...have a different meaning if changeover auto instead of Aux Loop function is disabled from the configuration tool S4 sensor is used to switch the controller operation mode to Energon Fan Coil Digital C...

Page 2: ...set at 9013 ModBus address 1 BUS output for Modbus supervisor connection 1 BUS output for STA60M or STA70M sensor connection For any customizations related to the controller configuration con tact th...

Page 3: ...I3 input digital 3 24Vac Summer Winter contact 37 DI4 input digital 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input...

Page 4: ...of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 4 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Change...

Page 5: ...pe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 5 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 6: ...e plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 6 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 7: ...pe plant with 24V 3 points valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 7 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 8: ...0 copper wire plait type twisted shielded braided and insulated The shield must be connected to controller GND pin 25 The network must be wired only in accordance with the principle shown here called...

Page 9: ...e the regula tion If the fan is connected to the relay output it is necessary to set the minimum fan speed parameter at 1 A system configuration with Proportional Fan requires setting the minimum spee...

Page 10: ...sed in parallel In case of use of 3 speed fans 3 relays the 0 10V outputs are always available and they follow the ON OFF or 3 point valves characteris tics The diagrams of the valves and fans share t...

Page 11: ...Propor tional Band as shown in the diagram aside 2 ON OFF Valves and 3 Speed FAN The valves are activated in ON OFF mode with a hysteresis Speed 1 2 and 3 follow to the Pro portional Band as shown in...

Page 12: ...alves 3 point or 0 10V and 3 speed fan The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 6 ON OFF V...

Page 13: ...llow the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated...

Page 14: ...luid is the RED LED NR9001 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top co ver and 2 LEDs to identify the state of the valves open or closed and th...

Page 15: ...Automatic changeover min set 10 35 20 Automatic changeover max set 10 35 30 Fan min limit set 10 55 35 Fan min limit hysteresis 0 10 3 Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay T...

Page 16: ...nt display STATUS WORD parameter NR9001 BIT Description 0 1 Default 0 Operation Mode Remote Disable digital input Comfort Economy and Power Off Local Enable digital input Comfort Economy and Power Off...

Page 17: ...of the schedule consists of setting the desired Tem perature Set for each band In addition to the Set there is also the possibility of setting the OFF sta tus which for the controller has the meaning...

Page 18: ...g the Knob it is possible to display cyclical ly the alarm error code the Modbus address of the controller and the main page ON OFF FAN buttons a long press of the two buttons allows entering the conf...

Page 19: ...e The parameters Dead band and Set Economy allow to determi ne the Set of Cold Set of Hot Dead band the set in Eco C Set C Rid Set the Eco Set F Set F Rid Set Instead for a more inuitive management th...

Page 20: ...ed in EEPROM memory The address can be changed only if the controller Dipswitch is not active If the STA70M sensor is present the Modbus address cannot be set by Supervision Contact our technical secr...

Page 21: ...performances stated in this sheet can be modified without any prior notice DIMENSIONS mm NR9001 STA60M STA60M 2 STA60MP STA60MP 2 86 86 8 22 55 28 48 74 60 74 60 1st Issue 06 2019 DBL585e Page 21 STA...

Reviews: