DIP switches 5-7 settings

DIP 5 DIP 6 DIP 7

CONFIGURATION DIAGRAM

OFF

OFF

OFF

ON/OFF Valves and 3 FAN speed (factory 

setting)

ON

OFF

OFF

ON/OFF Valves and 3 speed FAN - “FAST” 

operation mode (Operating Diagram 1)

OFF

ON

OFF

ON/OFF Valves and 3 speed FAN 

(Operating Diagram 2)

ON

ON

OFF

Proportional Valves (3 point or 0-10V) and 

3 FAN speed (Operating Diagram 3)

OFF

OFF

ON

ON/OFF Valves and 1 speed FAN 

(Operating Diagram 4)

ON

OFF

ON

Proportional Valves (3 point or 0-10V) and 

1 speed FAN (Operating Diagram 5)

OFF

ON

ON

ON/OFF Valves and Modulating FAN 

(0–10V) (Operating Diagram 6)

ON

ON

ON

Proportional Valves and Modulating FAN 

(0–10V). (Operating Diagram 7a e 7b)

To set the Operating Diagram 8

 is necessary to use the configurator 

leaving the DIP 5, 6 and 7 in OFF position.

DIP switche 8 settings

DIP 8

PLANT

OFF

2-pipe

ON

4-pipe

LEDs functionalities

Controller is equipped with 2 LEDs to check its behaviour and possi

-

ble anomalies as shown in the following table:

RED LED

GREEN LED

BLINKING 

RATE

DESCRIPTION

BLINKING

OFF

1Hz – DUTY 

CYCLE 50%

HOT VALVE OPENED

OFF

BLINKING

1Hz - DUTY 

CYCLE 50%

COOL VALVE OPENED

BLINKING

BLINKING

1Hz – DUTY 

CYCLE 10%

HOT & COOL VALVE 

CLOSED

ON

ON

NA

REMOTE SENSOR 

COMUNICATION 

FAILURE

ON

BLINKING

2Hz – DUTY 

CYCLE 50%

LOCAL SENSOR 

ERROR

Note: for a 2-pipe system the only connected 3-point or ON/OFF 

valve is the HOT valve and so the only operative LED for hot 

and cool fluid is the RED LED.

NR9001 CONTROLLER DIP SWITCHES AND LEDs

The controller has 8 DIP switches accessible by removing the top co

-

ver and 2 LEDs to identify the state of the valves (open or closed) and 

the communication anomalies.

1

2 3 4

5 6 7 8

ON

DIP switches from 1 to 4

 can be used to set MODBUS devices address 

(up to 14) without the use of the configuration tool and to set the 

controller in expansion mode duplicating the outputs.

If the first 4 DIPs are all in OFF, the default Modbus address is 1 (factory 

EEPROM setting).

In  the  case  of  more  than  14  controllers  the  configuration  can  be 

done either by supervision or through the configuration tool using the 

Modbus protocol.

DIP switches from 5 to 7 are used to set the operating diagram.

If the DIPs 5 to 7 are OFF, the default operating diagram is 2 - ON-OFF 

and 3 fan speeds (factory EEPROM setting).

DIP 8 is used to select a 2 or 4 pipe system.

If it is OFF, the system is 2-pipe (factory EEPROM setting).

The  settings  set  via  DIP  switches  have  priority  over  supervision.  It  is 

possible to disable the use of DIPs via the Modbus setting.

For each DIP setting change the controller must be switched off and 

on again.

DIP Switches 1-4 settings

DIP 1 DIP 2 DIP 3 DIP 4

MODBUS ADDRESS

OFF

OFF

OFF

OFF

Factory Setting 

(default address1)

ON

OFF

OFF

OFF

1

OFF

ON

OFF

OFF

2

ON

ON

OFF

OFF

3

OFF

OFF

ON

OFF

4

ON

OFF

ON

OFF

5

OFF

ON

ON

OFF

6

ON

ON

ON

OFF

7

OFF

OFF

OFF

ON

8

ON

OFF

OFF

ON

9

OFF

ON

OFF

ON

10

ON

ON

OFF

ON

11

OFF

OFF

ON

ON

12

ON

OFF

ON

ON

13

OFF

ON

ON

ON

14

ON

ON

ON

ON

Unexpected configuration

1

st

 Issue

06/2019

DBL585e

Page 14

Summary of Contents for Energon NR9001

Page 1: ...have a different meaning if changeover auto instead of Aux Loop function is disabled from the configuration tool S4 sensor is used to switch the controller operation mode to Energon Fan Coil Digital C...

Page 2: ...set at 9013 ModBus address 1 BUS output for Modbus supervisor connection 1 BUS output for STA60M or STA70M sensor connection For any customizations related to the controller configuration con tact th...

Page 3: ...I3 input digital 3 24Vac Summer Winter contact 37 DI4 input digital 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input...

Page 4: ...of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 4 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Change...

Page 5: ...pe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 5 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 6: ...e plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 6 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 7: ...pe plant with 24V 3 points valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 7 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 8: ...0 copper wire plait type twisted shielded braided and insulated The shield must be connected to controller GND pin 25 The network must be wired only in accordance with the principle shown here called...

Page 9: ...e the regula tion If the fan is connected to the relay output it is necessary to set the minimum fan speed parameter at 1 A system configuration with Proportional Fan requires setting the minimum spee...

Page 10: ...sed in parallel In case of use of 3 speed fans 3 relays the 0 10V outputs are always available and they follow the ON OFF or 3 point valves characteris tics The diagrams of the valves and fans share t...

Page 11: ...Propor tional Band as shown in the diagram aside 2 ON OFF Valves and 3 Speed FAN The valves are activated in ON OFF mode with a hysteresis Speed 1 2 and 3 follow to the Pro portional Band as shown in...

Page 12: ...alves 3 point or 0 10V and 3 speed fan The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 6 ON OFF V...

Page 13: ...llow the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated...

Page 14: ...luid is the RED LED NR9001 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top co ver and 2 LEDs to identify the state of the valves open or closed and th...

Page 15: ...Automatic changeover min set 10 35 20 Automatic changeover max set 10 35 30 Fan min limit set 10 55 35 Fan min limit hysteresis 0 10 3 Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay T...

Page 16: ...nt display STATUS WORD parameter NR9001 BIT Description 0 1 Default 0 Operation Mode Remote Disable digital input Comfort Economy and Power Off Local Enable digital input Comfort Economy and Power Off...

Page 17: ...of the schedule consists of setting the desired Tem perature Set for each band In addition to the Set there is also the possibility of setting the OFF sta tus which for the controller has the meaning...

Page 18: ...g the Knob it is possible to display cyclical ly the alarm error code the Modbus address of the controller and the main page ON OFF FAN buttons a long press of the two buttons allows entering the conf...

Page 19: ...e The parameters Dead band and Set Economy allow to determi ne the Set of Cold Set of Hot Dead band the set in Eco C Set C Rid Set the Eco Set F Set F Rid Set Instead for a more inuitive management th...

Page 20: ...ed in EEPROM memory The address can be changed only if the controller Dipswitch is not active If the STA70M sensor is present the Modbus address cannot be set by Supervision Contact our technical secr...

Page 21: ...performances stated in this sheet can be modified without any prior notice DIMENSIONS mm NR9001 STA60M STA60M 2 STA60MP STA60MP 2 86 86 8 22 55 28 48 74 60 74 60 1st Issue 06 2019 DBL585e Page 21 STA...

Reviews: