APPLICAZIONE ED USO

NR9001 is a digital controller for 2- or 4-pipe terminal units (eg. Fan 

Coil) with ON/OFF, 3-POINT floating or modulating control valves as 

well as with 3-speed or modulating fan. NR9001 is equipped with 

Modbus (SLAVE) communication protocol enabling the communi-

cation with other Modbus devices (MASTER). 

NR9001 is also equipped with a second Modbus communication bus 

dedicated to communicating with the sensors placed in the envi

-

ronment.

NR9001 is composed of an M6 module for DIN rail mounting and can 

be equipped with Modbus room sensors STA60M or STA70M. 

TECHNICAL CHARACTERISTICS

Power supply NR9001:  

 

85-265 Vac (isolated);

Protection Degree:    

 

IP 20;

Operation temperature: 

  

2T45°C;

Storage temperature:   

 

-25T65°C.

NR9001 controller inputs

• 

Digital Input (DI1) 

 

Window Contact

• 

Digital Input (DI2) 

 

Remote Power off / Badge 

(1)

• 

Digital Input (DI3) 

 

Winter/Summer Change Over

-

Digital Input (DI4) 

 

Comfort/Economy 

(1)

• 

Analogue Input (S1)    

Return Temperature Sensor 

(2)

Analogue Input (S2)   

Remote Temperature Set 

(2)

 

• 

Analogue Input (S3)   

Auxiliary loop sensor 

(3) (2)

• 

Analogue Input (S4)   

Auxiliary loop set selector 

(3) (2)

(1) 

Remote Power off” or “Comfort/Economy” digital inputs can be 

used to interface the controller with a Presence Detector to mini-

mize costs for heating and cooling.

  When digital inputs are in use they have priority on remote sensor 

and supervisory system. If, on the configurator is enabled “BADGE” 

function, the digital input DI4 loses its meaning, while the digital 

input DI2 enables the electrical loads and switches the operating 

mode between Comfort and Economy.

(2) 

Sensors with a sensing element NTC10K Ohm @ 25°C. 

  Accuracy ± 1K, β @ 25°C = 3435 

  (reference Controlli room sensors S4xxA/B and SNTC-xL)

(3) 

S3 and S4 inputs have a different meaning if “changeover auto” 

(instead of “Aux Loop”) function is disabled from the configuration 

tool. S4 sensor is used to switch the controller operation mode to 

Energon 

Fan Coil Digital Controller

NR9001

NR9001

CODE

DESCRIPTION

NR9001

Digital fan coil controller with Modbus sensors

STA60M

Modbus 24 Vac/dc temperature sensor

STA60MP

Flush-mounting Modbus 24 Vac/dc temperature sensor

STA60M-2

Wall mounting Modbus 24 Vac/dc temperature sensor

STA60MP-2

Flush-mounting Modbus 230 Vac temperature sensor

STA70M

Wall mounting remote 24 Vac/dc touch sensor

Summer or Winter on the basis of the fluid temperature and for fan 

minimum limit function. As an alternative this function can be asso

-

ciated to S3 sensor (if present). S3 sensor is used as minimum limit to 

hold the fun if fluid is not warm.

Digital  inputs  can  be  enabled  using  a  configuration  tool  called 

“Configuratore NR9001” thanks to which you can also reverse the in

-

puts action. It can be downloaded by our web site www.controlli.eu.

The default status of digital inputs (factory setting) is the following:

DIGITAL INPUT

DEFAULT

DESCRIPTION

WINDOW CONTACT 

(4)

N.C.(normally closed)

OPEN – window opened 

CLOSED – window closed

REMOTE POWER 

OFF

 

(4)

N.O.(normally open)

OPEN – comfort 

CLOSED – off (frost 

protection) 

(5)

WINTER/SUMMER 

CHANGEOVER

N.O.(normally open)

OPEN – Winter 

CLOSED – Summer

COMFORT/

ECONOMY 

(4)

N.O.(normally open)

APERTO – comfort 

CHIUSO – economy 

(5)

(4)

   These inputs are disabled by default (except winter/summer 

changeover, look at table page 16). If you need to enable them 

a supervisory system is required.

(5)

  See Badge function

For example, in case the window switch is normally opened (closed 

window is equivalent to open contact), it is necessary to reverse the 

action of the digital input.

NR9001 outputs

1

st

 Issue

06/2019

DBL585e

Page 1

STA60MP

STA70M

 The device contains electrical and electronic components and is not allowed to be disposed 

of as household refuse. All locally valid regulations and requirements must be observed.

Summary of Contents for Energon NR9001

Page 1: ...have a different meaning if changeover auto instead of Aux Loop function is disabled from the configuration tool S4 sensor is used to switch the controller operation mode to Energon Fan Coil Digital C...

Page 2: ...set at 9013 ModBus address 1 BUS output for Modbus supervisor connection 1 BUS output for STA60M or STA70M sensor connection For any customizations related to the controller configuration con tact th...

Page 3: ...I3 input digital 3 24Vac Summer Winter contact 37 DI4 input digital 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input...

Page 4: ...of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 4 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Change...

Page 5: ...pe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 5 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 6: ...e plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 6 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 7: ...pe plant with 24V 3 points valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 7 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 8: ...0 copper wire plait type twisted shielded braided and insulated The shield must be connected to controller GND pin 25 The network must be wired only in accordance with the principle shown here called...

Page 9: ...e the regula tion If the fan is connected to the relay output it is necessary to set the minimum fan speed parameter at 1 A system configuration with Proportional Fan requires setting the minimum spee...

Page 10: ...sed in parallel In case of use of 3 speed fans 3 relays the 0 10V outputs are always available and they follow the ON OFF or 3 point valves characteris tics The diagrams of the valves and fans share t...

Page 11: ...Propor tional Band as shown in the diagram aside 2 ON OFF Valves and 3 Speed FAN The valves are activated in ON OFF mode with a hysteresis Speed 1 2 and 3 follow to the Pro portional Band as shown in...

Page 12: ...alves 3 point or 0 10V and 3 speed fan The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 6 ON OFF V...

Page 13: ...llow the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated...

Page 14: ...luid is the RED LED NR9001 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top co ver and 2 LEDs to identify the state of the valves open or closed and th...

Page 15: ...Automatic changeover min set 10 35 20 Automatic changeover max set 10 35 30 Fan min limit set 10 55 35 Fan min limit hysteresis 0 10 3 Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay T...

Page 16: ...nt display STATUS WORD parameter NR9001 BIT Description 0 1 Default 0 Operation Mode Remote Disable digital input Comfort Economy and Power Off Local Enable digital input Comfort Economy and Power Off...

Page 17: ...of the schedule consists of setting the desired Tem perature Set for each band In addition to the Set there is also the possibility of setting the OFF sta tus which for the controller has the meaning...

Page 18: ...g the Knob it is possible to display cyclical ly the alarm error code the Modbus address of the controller and the main page ON OFF FAN buttons a long press of the two buttons allows entering the conf...

Page 19: ...e The parameters Dead band and Set Economy allow to determi ne the Set of Cold Set of Hot Dead band the set in Eco C Set C Rid Set the Eco Set F Set F Rid Set Instead for a more inuitive management th...

Page 20: ...ed in EEPROM memory The address can be changed only if the controller Dipswitch is not active If the STA70M sensor is present the Modbus address cannot be set by Supervision Contact our technical secr...

Page 21: ...performances stated in this sheet can be modified without any prior notice DIMENSIONS mm NR9001 STA60M STA60M 2 STA60MP STA60MP 2 86 86 8 22 55 28 48 74 60 74 60 1st Issue 06 2019 DBL585e Page 21 STA...

Reviews: