background image

OPERATION

The internally stored parameters used by the controller during op-

eration can be changed using STA60M or STA70M sensor or using 

a Supervisory System (MODBUS protocol). Remote Sensor NR9000-RT 

allows to change the operation mode, the set point and the fan 

speed; all other parameters can be modified only through the su

-

pervisory system or the dedicated configuration tool. The controller 

can operate also without the Remote Sensor using a dedicated an-

alogue input (Return Sensor).

The controller will consider the data acquired by the Sensor and by 

the Supervisory system (if present) and will perform a P or PI or PID 

regulation to drive the valves and the fan.

The controller can operate also without NR9000-RT and supervisory 

system (Modbus). In this case the room temperature is measured by 

the return sensor and thanks to the remote selector it is possible to set 

the correction of the temperature. In this configuration, the control 

parameters can be changed only through a dedicated configura

-

tion tool.

System configuration

The system can be configured as shown in the following diagrams:

• 

Cont Remote sensor

• 

Controller (Stand Alone) with return sensor

• 

N Contr N Remote s Supervisor

Supervisory system

• 

Operator Panel: MT-NET-PONR: it is possible to connect up to 50 

controllers.

• 

PC Supervisor: configuration tool “Configuratore NR9000” down

-

loadable from www.controlli.eu site; in this case it is possible to 

connect up to 250 controllers. It is possible to use also Micronet 

View or Touch Screen GTO series on demand getting in touch 

with our technical dept.; in this case it is possible to connect up 

to 48 controllers.

ModBus - RS485 Connection

The RS485 network is implemented with a 3-conductor cable, which 

will be later identified as “+” (pin 23), “-” (pin 24) and “GND” (pin 25). 

For wiring is suggested Belden®, model 8762.

For “disturbed” areas is suggested a Belden®, model 3106A using the 

twisted pair to connect the “+” and “-“, the reference wire to con-

nect to “GND” and the shield to connect to ground.

Alternatively you can use a cable with the following electrical and 

mechanical characteristics:

• 

AWG 20/22;

• 

characteristic impedance of 120Ω;

• 

copper wire, “plait” type, twisted;

• 

shielded braided and insulated;

The shield must be connected to controller GND (pin 25).

The  network  must  be  wired  only  in  accordance  with  the  principle 

shown here, called “daisy chain” (the device is composed by a sin

-

gle RS485 port). Star connections are not allowed.

Connections warnings

1. 

Do not use different types of cable to achieve the same net

-

work, but always use only the same type of cable;

2. 

The network cable carries out safety voltage signals (SELV) and 

must  not  be  wired  together  with  dangerous  voltage  signals 

(e.g., 230Vac) or carriers of high currents, especially if in alter-

nating current. Also avoid parallel paths to these power cables;

3. 

Wire the cable lying avoiding kinks, narrow bending radii and 

unnecessary wrapping in hanks or skeins;

4.  Do not twist the cable cord around the power conductors and, 

if they should cross, consider an intersection at 90 ° between the 

cable and these conductors;

5. 

Keep away from sources of electromagnetic field in particular 

by large motors, electrical cabinet, reactors for neon, all types 

of antennas;

6. 

Do not pull the power cable exceeds 110N (11.3kg) to prevent 

ironing;

7. 

Assess in advance the route so that it will be as short as possible 

and note addresses of connected instruments with particular 

reference to its location in the orderly sequence. This can be 

very useful in maintenance; we recommend to note the Mod

-

bus Address on the product label.

8. 

Do not reverse the polarity “+” and “-” of the connection ter

-

minals;

9. 

Avoid  short  lengths  of  cable  terminations  in  connection  tools 

to make a maintenance without tearing or flues of the cables 

possible;

10. 

Identify start and ending terminations and avoid cuts “open”;

Terminating resistors and network polarization

The slew rate control, mutual function in our 485 transceiver and the 

limited baud rate to 9600 baud make the terminating resistors not 

necessary.

RS485 network needs of polarization typically in charge of the master 

device; the controller doesn’t have polarization resistors.

The transceiver used by the controller allows to drive up to 256 points. 

RS485 standards require a maximum length of 1200m and/or 32 de-

vices on the network.

It should be noted that more limits are exceeded, higher is the prob-

ability that problems in communication arise. The phenomenon is not 

1

st

 Issue

06/2019

DBL585e

Page 8

Summary of Contents for Energon NR9001

Page 1: ...have a different meaning if changeover auto instead of Aux Loop function is disabled from the configuration tool S4 sensor is used to switch the controller operation mode to Energon Fan Coil Digital C...

Page 2: ...set at 9013 ModBus address 1 BUS output for Modbus supervisor connection 1 BUS output for STA60M or STA70M sensor connection For any customizations related to the controller configuration con tact th...

Page 3: ...I3 input digital 3 24Vac Summer Winter contact 37 DI4 input digital 4 24Vac Comfort economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input...

Page 4: ...of 4 pipe plant with 230V 3 point valves Example of 4 pipe plants with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 4 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Change...

Page 5: ...pe plants with 24V 3 point valves Example of 4 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 5 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 6: ...e plant with 230V 3 point valves Example of 2 pipe plant with 230V ON OFF valves 1st Issue 06 2019 DBL585e Page 6 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 7: ...pe plant with 24V 3 points valves Example of 2 pipe plant with 24V ON OFF valves 1st Issue 06 2019 DBL585e Page 7 Or fan min limit Or Changeover Auto Or Badge input Or fan min limit Or Changeover Auto...

Page 8: ...0 copper wire plait type twisted shielded braided and insulated The shield must be connected to controller GND pin 25 The network must be wired only in accordance with the principle shown here called...

Page 9: ...e the regula tion If the fan is connected to the relay output it is necessary to set the minimum fan speed parameter at 1 A system configuration with Proportional Fan requires setting the minimum spee...

Page 10: ...sed in parallel In case of use of 3 speed fans 3 relays the 0 10V outputs are always available and they follow the ON OFF or 3 point valves characteris tics The diagrams of the valves and fans share t...

Page 11: ...Propor tional Band as shown in the diagram aside 2 ON OFF Valves and 3 Speed FAN The valves are activated in ON OFF mode with a hysteresis Speed 1 2 and 3 follow to the Pro portional Band as shown in...

Page 12: ...alves 3 point or 0 10V and 3 speed fan The valves are activated in Pro portional mode 0 100 using a proportional band Speed 1 follows to the Proportion al Band as shown in the diagram aside 6 ON OFF V...

Page 13: ...llow the Proportion al Band as shown in the diagram aside generating a 0 10V output control signal 7b 0 5 6 10 V Sequence Valves and Proportional Speed Fan 0 10V 4 pipe plant The valves are activated...

Page 14: ...luid is the RED LED NR9001 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top co ver and 2 LEDs to identify the state of the valves open or closed and th...

Page 15: ...Automatic changeover min set 10 35 20 Automatic changeover max set 10 35 30 Fan min limit set 10 55 35 Fan min limit hysteresis 0 10 3 Operation Mode COMFORT 0 Economy 1 Frost 2 0 2 0 COMFORT Delay T...

Page 16: ...nt display STATUS WORD parameter NR9001 BIT Description 0 1 Default 0 Operation Mode Remote Disable digital input Comfort Economy and Power Off Local Enable digital input Comfort Economy and Power Off...

Page 17: ...of the schedule consists of setting the desired Tem perature Set for each band In addition to the Set there is also the possibility of setting the OFF sta tus which for the controller has the meaning...

Page 18: ...g the Knob it is possible to display cyclical ly the alarm error code the Modbus address of the controller and the main page ON OFF FAN buttons a long press of the two buttons allows entering the conf...

Page 19: ...e The parameters Dead band and Set Economy allow to determi ne the Set of Cold Set of Hot Dead band the set in Eco C Set C Rid Set the Eco Set F Set F Rid Set Instead for a more inuitive management th...

Page 20: ...ed in EEPROM memory The address can be changed only if the controller Dipswitch is not active If the STA70M sensor is present the Modbus address cannot be set by Supervision Contact our technical secr...

Page 21: ...performances stated in this sheet can be modified without any prior notice DIMENSIONS mm NR9001 STA60M STA60M 2 STA60MP STA60MP 2 86 86 8 22 55 28 48 74 60 74 60 1st Issue 06 2019 DBL585e Page 21 STA...

Reviews: