Table E-1
Drive ratings in 40°C ambient
Table E-2
Drive ratings in 50°C ambient
*No UL approval for Unidrive size 5 with 240A continuous in a 50°C ambient.
Model
Rating
Maximum permissible continuous output
current
Maximum
overload time
3kHz
4.5kHz
6kHz
9kHz
12kHz
60sec
UNI 1405
4kW
9.5A
8.5A
7A
5.5A
150%
UNI 2401
5.5kW
12A
11.7A
UNI 2402
7.5kW
16A
14.2A
11.7A
UNI 2403
11kW
25A
21.7A
18.2A
14.2A
11.7A
UNI 3401
15kW
34A
28A
23A
UNI 3402
18.5kW
40A
37A
28A
23A
UNI 3403
22kW
46A
40A
32A
26.6A
UNI 3404
30kW
60A
47A
40A
32A
26.7A
UNI 3405
37kW
70A
56A
46A
35A
28A
UNI 4401
45kW
96A
88A
70A
UNI 4402
55kW
124A
104A
88A
70A
UNI 4403
75kW
156A
124A
105A
80A
UNI 4404
90kW
180A
175A
145A
110A
UNI 4405
110kW
202A
175A
145A
110A
UNI 5401
300A
120%
Model
Rating
Maximum permissible continuous output
current
Maximum
overload time
3kHz
4.5kHz
6kHz
9kHz
12kHz
60sec
UNI 1405
4kW
6.9A
5.9A
5.1A
4.0A
3.3A
150%
UNI 2401
5.5kW
12A
11.6A
9.7A
UNI 2402
7.5kW
16A
14.7A
11.6A
9.7A
UNI 2403
11kW
20A
17.3A
14.7A
11.6A
9.7A
UNI 3401
15kW
34A
28A
21A
17.9A
UNI 3402
18.5kW
40A
34A
28A
21A
17.9A
UNI 3403
22kW
44A
36A
31A
24A
20.6A
UNI 3404
30kW
44A
36A
31A
24A
20.9A
UNI 3405
37kW
50A
41A
34A
26A
23A
UNI 4401
45kW
95A
85A
75A
60A
UNI 4402
55kW
105A
85A
75A
60A
UNI 4403
75kW
135A
105A
85A
65A
UNI 4404
90kW
180A
150A
125A
95A
UNI 4405
110kW
190A
150A
125A
95A
UNI 5401
240A*