Unidrive Regen Installation Guide
45
Issue Number: 2
www.controltechniques.com
Appendix F
Physical dimensions
The dimensions listed are for the following items, all of which are required to complete a Regen system. Note that the dimensions given apply only to
the parts specified in this guide.
Regen inductor
Soft start resistor
Switching frequency filter capacitor
Switching frequency filter inductor
RFI filter (Refer to the Unidrive Size 1 to 5 User Guide)
Varistors
F.1
Regen inductor
Table F-1
Specifications
Figure F-1
Type 1 dimensions
Drive
rating
(kW)
Amps
mH
L
D
H
WT
Kg
CT part
number
Type
number
4
9.5
6.32
200
180
215
12
4401-0001
1
5.5
12
5.00
200
180
215
14
4401-0002
1
7.5
16
3.75
240
180
270
17
4401-0003
1
11
25
2.40
240
180
270
24
4401-0004
2
15
34
1.76
320
220
325
32
4401-0005
2
18.5
40
1.50
320
220
325
33
4401-0006
2
22
46
1.30
320
220
325
39
4401-0007
2
30
60
1.00
360
260
370
55
4401-0008
2
37
70
0.78
360
260
370
65
4401-0009
2
45
96
0.63
360
280
370
75
4401-0010
3
55
124
0.48
360
280
370
95
4401-0011
3
75
156
0.38
410
300
430
110
4401-0012
3
90
180
0.33
410
300
430
120
4401-0013
3
110
220
0.30
480
320
490
130
4401-0014
3
160
300
0.24
480
320
490
140
4401-0015
3
20
5
SKOT TRANSFORMER LTD.
COPYRIGHT
200
120 fixing centres
20
APPX WEIGHT: 12kg
4 OFF 9
FIXING HOLE
180
140 fixing centres
6 way terminal block
for lead termination.
C
(mk6)
2 way terminal
block for thermister
termination (mk3)
PROJECTION
H
L
D