Reply (green)
Operating as Modbus Master, flashes green each time a good
response is received.
Operating as Modbus Slave, flashes green each time a good
response is sent.
Ethernet Activity
Green LED is on solid during portions of the boot-up process,
and then flashes briefly when Ethernet network traffic is
detected.
Ethernet Link
Yellow LED indicates an Ethernet link is present. This indicator
will light if a link is present regardless of processor or network
activity. If not lit, check network wiring.
Status
Blue LED (internal) on any time power is present and internal
power supply is functioning.
A.3 RS-485 Line Termination & Bias
Enable line termination only when this device is placed at the end of the network.
Termination should only be enabled at two points on the network, and these two
points must be specifically the end points.
Enable line bias when needed. Line bias should only be enabled at one point on the
network, and does not have to be the end point. Line bias holds the line in a known
neutral state when no devices are transmitting. Without bias, the transition from
offline to online by a transmitter can look like a false start bit and cause loss of
communication.
The line conditioning options are enabled when the respective shunt is moved to the
position indicated by the diagrams below.
Jumper locations for Babel Buster BB3-6101:
Jumper locations for Babel Buster MX-61: