Numbers in the First RTU Address In column must be unique. If an RTU address is
duplicated, only the first entry will be used.
When you have the unique situation of the TCP device being another gateaway, then
you have the option of mapping a range of RTU addresses to a single TCP IP address.
DO NOT duplicate IP addresses in the table. Duplicate IP addresses will not function
properly.
In the example below, the gateway will respond as RTU slaves 1 through 5. The unit
numbers in the requests forwarded to the TCP server at the given IP address will be
20 through 25.
When you have a long list of TCP devices, use the Prev and Next buttons to scroll
through the list. This gateway will support up to 120 connections to different TCP
devices.
5. Accessing TCP Devices from RTU