Description of application and parameters
Application program
28
NOTE
This parameter is only displayed when "Output is of type" is set on 1 byte 0 -
100% or 1 byte 0 - 255.
Options:
No
Yes
–
No
: The detector has a switch-off delay and, following the switch-off delay, transmits what
has been set under the "Value for switch-off" parameter.
–
Yes
: After the switch-off delay the detector first switches to the set reduced brightness and
only then sends the value set under the "Value for switch-off" parameter after brightness
reduced according to switch-off delay.
Example:
Switch-off delay of 5 minutes.
■
Value for switching off = 0%
■
Value for reduced brightness = 20%
■
Brightness reduced according to switch-off delay = 3 minutes
If movement is no longer detected, the light is dimmed to 20% after 5 minutes and then to 0%
after a further 3 minutes (switch-off).
Options:
0 .. 20 .. 100
– Here the value for the reduced brightness is set. After the switch-off delay has expired the
detector is to dim the light to this value.