Description of application and parameters
Application program
23
Options:
Master
Slave
–
Master
: In master mode On and Off telegrams are sent (to an actuator) dependent on
movement.
–
Slave
: In slave mode On telegrams are sent cyclically (to the "input slave or slave input" of a
master detector) when movement is detected.
Options:
No
Yes
–
No
: The option of receiving telegrams from a slave is not available.
–
Yes
: A 1-bit slave communication object (input) is being enabled. Via this input the master
detector receives the (On) telegrams of the connected slaves or of a push-button. An On
telegram from a slave is comparable with a detected movement.
Options:
1 bit
1 byte 0 - 100%
1 byte (0 - 255)
Light scene number 1 - 64
RTC operating mode switchover (1 byte)
–
1 bit
: intended for switch actuators.
–
1 byte 0 - 100%
: for activating dimmers.
–
1 byte 0 - 255
: for actuators, which are activated with a value of between 0 and 255.
–
Light scene number (1 - 64)
: for activating light scenes.
–
RTC operating mode switchover (1 byte)
: to directly switch room temperature controllers
into a specific operating mode.
■
Auto
■
Comfort
■
Standby
■
ECO
■
Frost/heat protection