EMS-96
Instruction Manual
IM1200-U v1.6
Pag. 42 / 48
Smart
It’s possible to define the measures which will be calculated the average, the minimum and the maximum in the period set
(from 1 minute to end of year).
Setup
Log
Smart
Smart Log (option)
Range
Default
Enable
yes / no
no
Enable or disable the smart log. Before to enable the log functionality, it’s necessary to disable any other activated log.
It is possible to use only one type of log at a time.
Analyse window
1 min
/
2 min
/
3 min
/
5 min
/
6 min / 10 min / 12 min / 15
min / 20 min / 30 min / 60 min / end of day / end of week /
end of month / end of year
15 min
Acquisition timing
Storage Type
FIFO / end memory
end memory
Type of storage. Note: FIFO after 10 consecutive cycles is automatically disabled.
Group 1
See Acronym Group table
---
Selection of the group for the 1
st
measure sampled for the smart log.
Measure 1
See acronym in the table of the group selected
---
Selection of the 1
st
measure sampled for the smart log.
………………..
………………..
Group 15
See Acronym Group table
---
Selection of the group for the 15
st
measure sampled for the smart log.
Measure 15
See acronym in the table of the group selected
---
Selection of the 15
st
measure sampled for the smart log.
Warning: All recordings for all log will be lost if any parameter is changed.
For an example, see the Generic Log.
To display how many log were acquired and the remaining storing time:
Information
L
og summary
Smart
.
To display the single log:
Information
L
og detail
Smart
.