EMS-96
Instruction Manual
IM1200-U v1.6
Pag. 39 / 48
Setup
Setpoint
Setpoint XX (from 1 to 32)
Range
Default
Enable
Yes / No
No
Enable or disable the setpoint function.
Source
Internal measures / Measures node X
Internal measures
Select the instrument from which the measure to analyze it will be read.
Group
See Acronyms Group table
---
Selection of the group for the actual setpoint if it is set
Internal measures
as
Source
.
Item
See acronym in the table of the group selected
---
Selection of the measure in the selected
Measure Group
of the actual setpoint.
High threshold
± 9999
0
The
Action
is executed if the measure exceed the set value.
High threshold unit
See below
See below underlined
With
Measure node X
as
Source
, the multiplier factor will be 1, 1000, 1000000 while with
Internal measures
there will be:
Voltage: mV-V-kV-MV
Reactive power: VAr-kVAr-MVAr–GVAr Angle: degree*10
Current: mA-A-kA-MA
Frequency: mHz
Apparent energy: VAh*100-kVAh-MVAh-GVAh
Apparent power:VA-kVA-MVA-GVA Temperature: °C
Active energy: Wh*100-kWh-MWh-GWh
Active power: W-kW-MW-GW
THD and harmonics: %*100
Reactive energy: VArh*100-kVArh-MVArh-GVArh
Low threshold
± 9999
0
The
Action
is executed if the measure is lower than the set value.
Low threshold unit
See below
See below underlined
See the description of
High threshold unit
.
Over debounce [seconds]
0 ÷ 10000
0
0: instantaneous execution of the
Action
1÷10000: execution of the
Action
if the condition is kept for the time set
Entry debounce [seconds]
0 ÷ 10000
0
0: instantaneous execution of the
Action
1÷10000: execution of the
Action
if the condition is kept for the time set
Hysteresis (for high & low threshold)
See below
0
Setting a value different by 0, the hysteresis is enabled with a percentage value set.
Logic operation over
See below
no logic
- No logic: the
Action
is executed without to verify the status of others setpoint [Default].
- OR logic: the
Action
is execute after the check of result of the OR logic operation with the setpoint selected in operands.
- AND logic: the
Action
is execute after the check of result of the AND logic operation with the setpoint selected in operands.
WARNING:
it’s not possible to set OR logic for logic operation over and logic operation entry at the same time.
Logic operation entry
See below
no logic
- No logic: the
Action
is executed without to verify the status of others setpoint [Default].
- OR logic: the
Action
is execute after the check of result of the OR logic operation with the setpoint selected in operands.
- AND logic: the
Action
is execute after the check of result of the AND logic operation with the setpoint selected in operands.
WARNING:
it’s not possible to set OR logic for logic operation over and logic operation entry at the same time.
Operands (1-16)
See below
No Operands
Setpoint 1: select Yes to include the setpoint 01 in the logic.
- - - - - - - - - - - - - - - - - - -
Setpoint 16: select Yes to include the setpoint 16 in the logic.
Operands (17-32)
See below
No Operands
Setpoint 17: select Yes to include the setpoint 17 in the logic.
- - - - - - - - - - - - - - - - - - -
Setpoint 32: select Yes to include the setpoint 32 in the logic.
Action over
See below
None
It possible to select one, more or anything action:
- Display and save the event.
- Increase a variable that indicates the number of events.
- Change the DO-X state.
- Increase a variable that indicates the duration time of the event.
Action entry
See below
None
It possible to select one, more or anything action:
- Display and save the event.
- Change the DO-X state
DO used
See below
None
It possible to select (with Yes) one or more DO: DO-1, DO-2, DO-3, DO-4, DO-5, DO-6, DO-7, DO-8.
WARNING:
for a correct functioning before to select the output it’s necessary to set the SETPOINT mode under the item MODE in
the setup page of the DO group (DO-1, 2, 3, 4 or DO-5, 6, 7, 8).