EMS-96
Instruction Manual
IM1200-U v1.6
Pag. 30 / 48
Energies and Counters
The
EMS-96
has
4,
8
or
16
timebands
(depending
of
the
option)
to
differentiate
the
power
consumption.
You
can
schedule
the
exchange
of
the
timebands
using
manual
(Modbus
command),
from
DI
(digital
inputs)
or
Preset
(
Setup
Timeband
Mode
Preset
).
With
from DI
it’s necessary to set the use of digital inputs for this purpose (
Setup
I/O
DI 1, 2, 3, 4
Mode
Change TB
).
With
Preset
it is necessary to define a
Daily plan
in which you set the time of transition (maximum 16) from one to the next
timeband. In the setting of
Period plan
(
Setup
Timeband
Preset
Daily/Period
Plan
) it will be selected the month and the day
of the start and the end, and it will be necessary to link each
Daily Plan
to one or more days of the week. At the end of settings
the
Period Plan
will be enabled. Any holidays will be set in the menu
Holidays
(
Settings
Timeband
Preset
Holidays
).
Setup
Measure
Energies/Counters
Mode
Mode Timeband (option)
Range
Default
Energy changing
manual / from DI / preset
manual
It’s possible to select the modality to change the timeband:
-
Manual.
-
From DI: the combination of digital inputs select the actual timeband (TB) used (see the following table).
-
Preset (see timeband Daily and Period plan for more information).
Counter changing
manual / from DI
manual
It’s possible to select the modality for change the timeband:
-
Manual.
-
From DI: the combination of digital input select the actual timeband (TB) used (see the following table).
DI4
DI3
DI2
DI1
TB used
DI4
DI3
DI2
DI1
TB used
DI4
DI3
DI2
DI1
TB used
DI4
DI3
DI2
DI1
TB used
0
0
0
0
1
0
1
0
0
5
1
0
0
0
9
1
1
0
0
13
0
0
0
1
2
0
1
0
1
6
1
0
0
1
10
1
1
0
1
14
0
0
1
0
3
0
1
1
0
7
1
0
1
0
11
1
1
1
0
15
0
0
1
1
4
0
1
1
1
8
1
0
1
1
12
1
1
1
1
16
Setup
Measure
Energies/Counters
Daily plan
Daily Plan X (from 1 to 16) (option)
Range
Default
Start Hour 1
00 ÷ 23
0
Hour at which the timeband will be changed.
Start Minute 1
00 ÷ 59
0
Minute at which the timeband will be changed.
Timeband Used 1
not used ÷ TB-XX* (band)
not used
New Timeband set.
………………..
………………..
Start Hour 16
00 ÷ 23
0
Hour at which the timeband will be changed.
Start Minute 16
00 ÷ 59
0
Minute at which the timeband will be changed.
Timeband Used 16
not used ÷ TB-XX* (band)
not used
New Timeband set.
* XX in TB-XX, depends from the number of the Timeband enabled.
Setup
Measure
Energies/Counters
Period plan
Period Plan X (from 1 to 16) (option)
Range
Default
Enable
yes / no
no
Enable or disable the plan.
WARNING
: Set all the following parameters before to enable it.
Start Month
January ÷ December
January
Month at which the period start.
Start Day
1 ÷ 31
1
Day at which the period start.
End Month
January ÷ December
December
Month at which the period finish.
End Day
1 ÷ 31
31
Day at which the period finish.
Monday Plan
Plan 1 ÷ Plan 16
Plan 1
Plan used for this day.
………………..
………………..
Sunday Plan
Plan 1 ÷ Plan 16
Plan 1
Plan used for this day.