9
W415-0318 / 03.05.09
2.2.1
OUTSIDE: Slip the one end of a liner a minimum of 2" over the collar of the
air terminal. Secure using 3 screws. Then seal the joint and screw heads
with high temperature sealant. Repeat with the other liner to the exhaust
collar of the terminal.
NOTE: Connect the supplied 3' of stainless steel
fl
ex liner to the
exhaust liner (already attached to the terminal) using the coupler
(also supplied). Secure and seal before dropping down the
chimney.
2.2.2
Gently stretch the liners to the required lengths and insert into the
chimney. Place the terminal onto the top of the chimney cap and fi t
the fl ashing plate to suit. Make weather tight by sealing with caulking
(not supplied) and fasten to the chimney with screws and plugs
(not supplied).
2.2.3 NOTE:
If there is not enough ceiling height between the
fi
replace and
the insert to allow the
fl
ex liner connection on the top of the unit to be
made, see 2.2.4.
If there is enough ceiling height, connect the 3" stainless steel fl ex liner to
the exhaust collar closest to the top front on the unit. Connect the intake
fl ex liner to the remaining rear collar. Secure and seal.
2.2.4
Both the log support and the back wall must be removed in
order to gain access to the vent connection assembly.
Both the back wall and log support are detached by removing
the 12 perimeter screws of the back wall and the 3 screws
located at the back of the log support. Remove the vent
connection assembly.
NOTE: The vent connection
assembly collars are not speci
fi
c until the stainless
steel
fl
ex liner has been attached to one side. This
now designates the side as exhaust. The exhaust
collar must be positioned closest to the front
opening of the insert. Secure and seal the
fl
ex liners.
2.2.5
To reinstall the vent connection assembly, reach in
through the insert and manoeuvre the vent connection
assembly through the opening in the fi rebox top. Take
care not to damage the gasket. Secure the assembly
using the four studs and ¼-20
hex nuts.
2.2.6
Reinstall the back wall, followed
by the log support, using the
perimeter screws removed in
2.2.4. The insert may now be
pushed into its fi nal position
inside the wood burning fi replace.
Secure the insert to the fi replace
using perforated strapping attached to the two securing holes on
either side of the unit as shown. We recommend that the trim be
installed before the unit is placed into its fi nal position.
ALUMINUM
FLEX LINER
COUPLER
STAINLESS
STEEL
FLEX LINER
FIGURE 2.2.2
FIGURE 2.2.4a
BACK WALL
LOG SUPPORT
FIGURE 2.2.4b
VENT CONNECTION
ASSEMBLY
FIGURE 2.2.5
VENT
CONNECTION
ASSEMBLY
FIGURE 2.2.6a
2" OVERLAP
SEALANT
HI-TEMP
VENT
CONNECTION
ASSEMBLY
FIGURE 2.2.1
FLASHING
PLATE
2"
OVERLAP
SEALANT
HI-TEMP
EXHAUST
INTAKE
SECURING
HOLES
FIGURE 2.2.6b