Operation Manual
Regulator
4 kW 560 V DC 40% Duty Cycle + 24 V DC
BAL9100-0126d-EN
www.conductix.com
original document
page 25 of 32
status relay
closed
status relay
open
error relay
open
warning relay
is closed
see a) or b)
see c)
see d)
warning relay
is open
normal operation:
see chapter 10.2
normal operation:
see chapter 10.2
see e)
Table 1: Relay outputs and meaning
green LED remains ON
(Status relay closed)
green LED is blinking
(Status relay open)
red LED remains ON
(Error relay open)
orange LED
remains ON
(warning relay closed)
see a)
X
X
orange LED
is blinking
(warning relay closed)
see b)
see c)
see d)
orange LED
is OFF
(warning relay open)
normal operation:
see chapter 10.2
normal operation:
see chapter 10.2
see e)
white LED
remains ON
(no relay relevant)
normal operation:
see chapter 10.2
X
X
white LED
is OFF
(warning relay open)
see f)
normal operation:
see chapter 10.2
see e)
Table 2: LED display and meaning
a)
The maximum peak power available is exceeded. Refer to chapter 4.1 “Electrical Data”, 7.5 “Place and Conditions of
Installation” and 8.3 ”Positional Tolerances” to make sure the requirements in peak power match the actual conditions of
operation.
b)
The internal temperature is approaching maximum ratings. If the continuous power consumed is compatible with the specified
technical data (chapter 4.1 and 4.2) and together in accordance with chapter 7.5 “Place and Conditions of Installation”, this
warning will have no consequence and the system may be further operated as it is. On the other hand, if such a warning
appears in the long run, whereas it was never displayed before, this may indicate for example a strong soiling of the cooling
elements and we therefore strongly recommend referring to chapter 11 “Maintenance”. This situation may lead to an over
temperature error: see case d).