4
Technical Data
The data specified in this section are valid only if the requirements regarding the environment of the device
(position, ambient temperature etc…) are respected.
For instance, the layout of the IPT
®
track, the variations with respect to nominal position of a Pickup, or the
ambient temperature around a Regulator, may lead to a reduction of the peak and/or continuous power
available.
Regulators and Pickups are not designed for independent operation. Refer to both operation manuals
together.
4.1
Electrical Data
•
Input
4 kW Pickup, 20 kHz (see chapter 14.1)
•
Output voltage 1
560 V DC +/-25 V AC
•
Output current 1
8 A DC maximum
•
Peak output power
4 kW
in sum for both output 1+ 2 and under adequate
condition of operation (see chapter 7.5 and chapter 8.3).
•
Continuous output power
1,6 kW at 40°C ambient = 40% duty cycle
2,5 kW at 20°C ambient
over 10 minute periods, air convection 0,1 m/s and nominal position
(see chapter 7.5).
in sum for both output 1 and 2
•
Output 2
24 V DC +/-5%
5 A DC
based on the output voltage 1 (see chapter 10.2 and chapter 10.3)
do not overload
maximal short-circuit current: 11 A DC
•
Heat loss
Approximately 400 W at full load.
•
Electrical protection
Class II (reinforced internal insulation)
•
Insulation
Output 1 to Ground / Output 2 / Interface: production tested at 5 kV DC / 5 s.
Output 2 / Interface to Ground tested at 500 V DC / 5 s.