42 | Maintenance
2588787_B_EN_2005_US_OM
US
Component
Frequency
Description
UV assembly
Weekly -
Monthly
Inspect for any damage. Replace annually, or as necessary before 10,000
hours of use. Refer to
"Removing and Installing the UV Assembly" on
Ultrasonic
Blower Pack
Weekly -
Monthly
Clean and disinfect the flexible tubes and mist channel weekly. If results from
inspections are satisfactory (as per your risk assessor), flexible tubes and
channels may be cleaned monthly. Refer to the Ultrasonic Blower Pack
Installation, Operation, and Maintenance Manual.
Reverse
Osmosis System
Monthly -
Annually
Replace membranes and filters as necessary. Refer to the Reverse Osmosis
System Installation, Operation, and Maintenance Manual.
Air filters
Weekly -
Monthly
Replace all air filters for air leading to the humidifier and Ultrasonic Blower
Pack. If the air quality is bad, replace the air filters weekly, and if the air quality is
good, replace the air filter monthly. Depending on performance and air quality,
this may be extended — contact your Condair representative.
2
3
1
4
5
6
7
Figure 13 -
Components to clean in the Ultrasonic Humidifier
1.
Hoses
2.
Fill valve
3.
Strainer
4.
Fill cup
5.
Fill cup cover
6.
Drain valve
7.
Drain cup