2
Water Supply Requirements to the US (after treatment with RO and/or DI)
Conditions
Value
Pressure
2-5.5 bar (30-80 psi)
spike pressure limited to 8 bar (120 psi)
Temperature
1-25 °C (34-77 °F)
Min-Max Conductivity * , Max Total
Dissolved Solids (TDS)
2-15 µS/cm , TDS: 9 mg/L
Quality
RO or DI water
refer to the water supply requirements for the RO-U
Colony-forming Unit (CFU)
< 200 CFU/ml for industrial applications**
follow applicable regulations
* if the conductivity of the water entering the RO-U system is greater than 350 µS/cm, contact your Condair
representative .
** CFU leaving the unit via mist should be <1000 CFU/ml for industrial applications. Keep the CFU entering the
humidifier as low as possible, such that the CFU leaving the unit is within acceptable guidelines.
5.1.3
Fill Rate
Fill Rate
US 7-20
Minimum: 3.3 L/min (0.9 gpm)
Maximum: 8.7 L/min (2.3 gpm)
US 40*
Minimum: 6.6 L/min (1.8 gpm)
Maximum: 17.4 L/min (4.6 gpm)
(3.3 L/min (0.9 gpm) per reservoir)
Note:
* The US 40 has two reservoirs
5.1.4
Drain Rate
Drain Water
US 7-40
Minimum: 8.7 L/min (2.3 gpm)
US 40*
Minimum: 17.4 L/min (4.6 gpm)
(8.7 L/min (2.3 gpm) per reservoir)
Note:
* The US 40 has two reservoirs
US
2588787_B_EN_2005_US_OM
Product Specifications | 21