5.2
Operating Data
5.2.1
Control Signal
Control Signal Type:
Active
0-5 VDC, 1-5 VDC, 0-10 VDC, 2-10 VDC, 0-20 VDC, 0-16 VDC, 0-20 mADC, 4-20
mADC
Passive
135-10kΩ ohmic humidity sensor
On/Off Control
< 9.5 VDC Off
15-24 VDC On
5.2.2
Ambient Conditions
Ambient Conditions:
Ambient Temperature
5-40 °C (41-104 °F)
Relative Humidity
5-95% RH non-condensing
Refer to
for the maximum external fusing (single-phase) for the Ultrasonic Humidifier.Refer to
for the maximum external fusing (single-phase) for the Ultrasonic Blower Pack.
Table 8:
Ultrasonic Humidifier, Maximum External Fusing — Single-Phase
Mod
el
110-120V/1~
208V/1~
220-240V/1~
Maxim
um
Output
Maxim
um
Curren
t
Maximu
m
External
Disconn
ect
Maxim
um
Output
Maxim
um
Curren
t
Maximu
m
External
Disconn
ect
Maxim
um
Output
Maxim
um
Curren
t
Maximu
m
External
Disconn
ect
US 7
744 W
6.2 A
15 A
744 W
3.6 A
15 A
744 W
3.1 A
15 A
US
13
744 W
6.2 A
15 A
744 W
3.6 A
15 A
744 W
3.1 A
15 A
US
20
744 W
6.2 A
15 A
744 W
3.6 A
15 A
744 W
3.1 A
15 A
US
40
1440 W
12.0 A
15 A
1440 W
7.0 A
15 A
1440 W
6.0 A
15 A
US
2588787_B_EN_2005_US_OM
Product Specifications | 23
Summary of Contents for US 13