Replacing the water level unit
1. Take the humidifier out of operation, as described in chapter 7.4.
2. Undo the brackets and open the left front panel
3. Remove the connection cable to the level unit.
4. Remove hose clamps on the level unit connections and pull off the hoses.
5 Squeeze both sides of the mounting bracket to release it from the slots in the support bracket behind
the water level unit, then remove the level unit.
Reinstallation is carried out in the reverse sequence. Make sure the hose are correctly secured with
the hose clamps and the cable is connected correctly.