50
Components
Interval
Work required
I
II
III
Flue gas temperature sensor
X
X
Visual check that sensor is intact, wired and attached to
the exhaust.
Flue gas outlet pipe
X
X Check flue gas outlet pipe for sealing and remove all traces of
condensate. If specified, have the flue gas system inspected
by an appropriate specialist.
Igniter and flame sensor
X
Every year or every 2000 hours (which is reached first).
Remove and replace igniter and flame sensor (special spares
set “Burner parts subject to wear”).
Burner / combustion air blower
X Remove burner and inspect the condition of burner mat. Blow
out burner mat with compressed air or replace burner if neces-
sary. Replace all burner seals with new ones (special spares
set “Burner parts subject to wear”).
Clean combustion air blower if necessary. The electric motors
of the blowers are provided with permanent lubrication and do
not require maintenance.