Installation notes
The following instruction notes must be observed:
–
Flue gas specifications: ---> see table in chapter 10.2
– The flue gas temperature during normal application and when the maintenance schedule is fulfilled is
between 160 180 °C. If the unit is not maintained properly the flue gas temperature could increase.
In this case the temperature switch would shut down the unit if the temperature exceeds 200 °C for
safety reasons.
– Use the supplied flue gas pipe with storm collar and rain cap exclusively.
– The supplied flue pipe extension and the rain cap have builtin mechanical locking band and gasket.
Simply push each component to the stop bead, which provides an air and watertight seal. Then,
tighten the integrated locking band on each component to complete the installation of the flue gas
venting.
– Make sure the rain cap is at least 60 cm above any ridge within 3 m of the unit.
Note
: if the flue gas venting needs to be longer for any reason please contact your Condair repre
sentative.