Gas installation
Installation notes
The gas supply pipe must be connected to the connection on the unit via a shutoff valve (essential
requirement), which is installed in the immediate vicinity of the unit.
When steel gas pipes are in use,
it is essential that a sediment separator be fitted
between the shutoff valve and the unit connection.
The following connection data must be adhered to:
– Permissible gas operating pressure
Gas
Operating pressure (mbar)
Nominal Min Max
Natural gas H, E, E(S)
G20
20
17
25
Natural gas L, ELL
G25
25
20
30
Natural gas HS
G25.1
25
20
30
Natural gas Lw
G27
20
17.5
23
Natural gas Ls
GZ350
13
10.5
16
Propane Gas P
G31
37 or 50
25
57.5
– The connection material used must be
pressure tested
and
approved for gas installations
.
–
Do not
use teflon tape on gas line pipe threads. A flexible sealant suitable for use with Natural Gas
and Propane Gas is recommended.
– Plan gas supply piping so it will not interfere with removal of gas valves or blower assemblies and
front or side service doors.
All installation work must be carried out in accordance with
the applicable local building
and installation regulations
.
All work concerning the water installation must be performed only by
adequately qualified
personnel
(e.g. plumbers). Ascertaining the qualifications is the customers responsibility.
Warning - danger of electric shock!
For all installation work, the Condair GS...OC
must be
disconnected from the mains supply
and
secured against unintentional reconnection
.
5.5.1 Performing the gas installation
Overview Gas installation
1 Gas supply connection
Model
Connection
GS 40 OC
BSP 1/2"
GS 80 OC
BSP 3/4"
GS 120 OC and GS 160 OC BSP 1"
GS 200 OC and GS 240 OC BSP 1 1/4"
2 Gas shut-off valve (building side)
3 Sediment trap
(Installation - building side - essential in the case
of the use of steel gas pipes)
3
2
1