19
OUTPUT RELAYS PAGE
The Advantium16 output relays page shows the current configuration for each of the
systems output relays. Each row represents the configuration for the dry contact output
relay of that number. The settings may be changed by selecting the appropriate value
from the drop-down box, or clicking the appropriate check box and clicking the set
button. The cancel button will restore the current settings if any have been made in the
browser but not committed.
If an output is disabled, the circuit will be open or closed at all times depending on the
jumper setting.
The source indicates whether individual input relays or input groups should be used to
determine whether the output relay exits normal condition. If "Relay" is chosen, the
numbers at the right of the row (1-16) correspond to the number of the input relay (see
the
Inputs
settings page for configuration information). If "Group" is chosen, the numbers
at the right of the row (1-16) correspond to the number of the input group (see the
Inputs
settings page for configuration information).
The event indicates the condition in which the output will alarm. If “All” is selected, then
all of the selected inputs must enter an alarm condition for the output to exit its normal
condition. If “Any” is chosen, then any of the selected relays entering alarm condition
will cause the output relay to exit its normal condition.
Each input checked will be monitored for alarm if enabled. If the selected input is
disabled, it will be ignored.