Concoa Advantium 16 Installation And Operating Instructions Manual Download Page 20

18 

 

 

INPUT GROUPS PAGE 

The Advantium 16 Input Groups page shows the current configuration for Input groups. 
Each row represents the configuration for the Input Group of that number. The settings 
may be changed by clicking the appropriate check box and clicking the set button. The 
cancel button will restore the current settings if any have been made in the browser but 
not committed.  

 

If ALL of the enabled members of an input group enter an alarm condition, then the 
multi-color LED for each input will blink red. Input groups may also be referenced in the 
configuration of output relays. To be used, an input group must have at least one 
member.  
 
If an input group is disabled, none of the multi-color LEDs for member inputs will blink 
red when all enter alarm condition. Additionally, if the input group is referenced for an 
output event, it (and all members) will be ignored. Please note, however, that disabling an 
input group does not disable input group members. Inputs may only be disabled on the 
Inputs configuration page.  
 
The name of the input group is used on the status page of this website and in any e-mails 
generated.  
 
A group would typically be created for each continuous gas delivery system. For 
example, a group entitled "Carbon Dioxide Switchover" might contain a "Right Side" 
input and "Left Side" input.

  

 

Figure 17 

 

 

 

Summary of Contents for Advantium 16

Page 1: ...ATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 Telephone 1 800 225 0473 or 757 422...

Page 2: ...ENVIRONMENTS DO NOT INSTALL THIS PRODUCT IN ANY HAZARDOUS ENVIRONMENT If product appears damaged in any way do not use and request service from CONCOA USER RESPONSIBILITY Service to this product shou...

Page 3: ...he Advantium 16 6 Connecting Alarm Outputs 11 Setting Remote Alarm Outputs 12 Muting Audible Alarm 14 Real Time Clock 14 Configuration using the WebServer 15 Status Page 15 View Settings Page 16 Chang...

Page 4: ...tage External Power Supply Universal input voltage 100 240 VAC 50 60Hz Power Consumption 8 watts ALARM OUTPUT RELAY SPECIFICATIONS Contacts Normally Open Normally Closed selectable Dry Contact Contact...

Page 5: ...contains two relay output signals and a shared common voltage input The Advantium 16 is factory set so that these output signals are brought out through Normally Closed N C contacts Output relay signa...

Page 6: ...s The Advantium16 uses Normally Closed N C contact signals by default from the external inputs to determine the state of the alarms The normal conditions of these alarms are customizable via the web i...

Page 7: ...5 MOUNTING REQUIREMENTS Figure 2...

Page 8: ...to interface with up to 16 external pressure switches or any dry contact inputs The external device wires 12Vdc out signal in are brought in through a conduit connector on the left side of the box an...

Page 9: ...7 Figure 4...

Page 10: ...8 Figure 5 Figure 6 Figure 7 See Figure 4 for Available Cable Lengths Cable Ass y 5295349 L Figure 8...

Page 11: ...9 Figure 9...

Page 12: ...e Figure 10 below The relay contacts are configurable They are factory set as Normally Closed N C but may be changed to Normally Open N O if needed Refer to the Section Setting Remote Alarm Outputs in...

Page 13: ...rm from AC power 2 Open the unit by loosening the 6 screws located on the front of the enclosure 3 Figure 11 shows the location of the jumpers on the circuit board for setting the contacts 4 Using Tab...

Page 14: ...lay Output 4 J16 Relay Output 5 J18 Relay Output 6 J21 Relay Output 7 J23 Relay Output 8 J26 Relay Output 9 J28 Relay Output 10 J31 Relay Output 11 J33 Relay Output 12 J36 Relay Output 13 J40 Relay Ou...

Page 15: ...In order to re enable the audio alarm press and hold the alarm for five seconds again The speaker will sound once indicating the audio alarm is enabled REAL TIME CLOCK The Advantium 16 has a battery b...

Page 16: ...GE The Advantium 16 webserver Status screen is essentially a copy of the front panel of the Advantium 16 unit Each of the front panel LED s and labels are represented and colored RED or GREEN based on...

Page 17: ...splays two system parameters Webserver Software version and FPGA version An export settings button on the page allows for exporting data into a text file This includes all of the Advantium 16 system p...

Page 18: ...ge shows the current settings for the date time and system ID When utilizing more than one Advantium 16 control system the System ID can be used to differentiate the units in the email subject line Th...

Page 19: ...is disabled it will be ignored and the LED will be turned off The name of the input is used on the status page and in any generated emails The normal condition of the input indicates the expected cir...

Page 20: ...onfiguration of output relays To be used an input group must have at least one member If an input group is disabled none of the multi color LEDs for member inputs will blink red when all enter alarm c...

Page 21: ...should be used to determine whether the output relay exits normal condition If Relay is chosen the numbers at the right of the row 1 16 correspond to the number of the input relay see the Inputs sett...

Page 22: ...determine whether the e mail alert will be triggered If Relay is chosen the numbers at the right of the row 1 16 correspond to the number of the input relay see the Inputs settings page for configura...

Page 23: ...tory default security settings To enable security enter a password twice click the desired Security Enabled box and click the set button The cancel button will restore the current settings if any have...

Page 24: ...f any have been made in the browser but not committed Any change to the IP settings will immediately cause the server to restart therefore please ensure access to the new network location prior to cli...

Page 25: ...get host To force all mail to be sent via relay regardless of the recipient domain enter the name or address of the relay server in RELAY ADRESS If this setting is blank the SMTP server on the Advanti...

Page 26: ...obligation and Buyer s sole and exclusive remedy under the above warranties is limited to repairing using new or reconditioned parts or replacing free of charge except for labor if permanently install...

Page 27: ...25...

Page 28: ...26 Certified ISO 9001 Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 Telephone 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com...

Reviews: