CONFIGURATION USING THE WEBSERVER
The Advantium 16 is equipped with an integral web server as a means for remote
monitoring and configuration of the system. Connection to the webserver is achieved
through an RJ45 connector located on the left hand side of the unit. Refer to the
Advantium 16 Webserver Configuration Instructions for connection instructions,
including factory default network and security settings. The internal reset button is used
to restore factory network settings if necessary.
The Advantium 16 webserver has a number of useful status and configuration pages that
will be explained in greater detail in the subsequent tabs/pages.
STATUS PAGE
The Advantium 16 webserver Status screen is essentially a copy of the front panel of the
Advantium 16 unit. Each of the front panel LED’s and labels are represented and colored
RED or GREEN based on alarm status. Also a copy of the last 20 events in the on board
event log are displayed at the bottom of the screen. An Export Log button at the bottom
also allows for exporting of the entire event log in csv format.
The system event log has a maximum size of 500 Kb. When the event log reaches 90% of
the maximum size, a warning email will be sent to all enabled email recipients. When the
event log reaches capacity, no new items will be added to the log. New events will
continue to be displayed in the “Recent Events” portion of the Status page and every
subsequent email sent from the Advantium 16 will have “(Event Log full)” appended to
the subject line.