CONNECTING ALARM OUTPUTS
The
Advantium
16 provides output signals corresponding to the alarm conditions that it
senses. These signals are presented through relay contacts and are brought out to
terminal connectors on the right hand side of the circuit board connector at the bottom of
the alarm. They are then routed through the conduit connector on the left side of the box
(See Figure 10 below). The relay contacts are configurable. They are factory set as
Normally Closed (N.C.) but may be changed to Normally Open (N.O.) if needed. Refer
to the Section “Setting Remote Alarm Outputs” in the manual for the procedure.
The recommended cable for making an output cable assembly is 14-26 AWG. The length
of each cable should be limited to 1500 feet.
Cut the cable to length. Remove the outer jacket of the cable to expose approximately 3/4
inch of the internal conductors on both sides of the cable. Strip away 1/4-inch of the
insulation on each of the conductors.